PACMotion VFD Syllabus
Section 12
GFK-3167B
December 2020
PACMotion VFD Fieldbus Option Modules and Setup (Note 8)
55
12.4.8
PROFINET
F
IELDBUS
O
PTION
M
ODULE
Option Module Details: PROFINET Option Card for VFD Part Number: IC866-OC-P
The PROFINET option card permits the PACMotion VFD Drive to connect to a PROFINET
network.
PROFINET Option Card
RJ45 Connectors & Network
Activity LEDs, PROFINET Option
Card
[1]
LED: NS
[A]
LED: Activity
[2]
RJ45: P1
[B]
LED: Link
[3]
Labeling: PROFINET I/O
[4]
RJ45: P2
[5]
LED: MS
12.4.9
Bus Specific Technical Data
Baud rate
10/100 Mbaud in full-duplex mode
Connection technology
2 × RJ45
12.4.10
Hardware Insertion and Removal
Remove power from the VFD. Using a T09 driver bit, backout the option module 2 screws
approximately 4 or 5 turns each. This should allow the locking tabs to retract to a flat
position. Insert the module into the VFD Fieldbus option module cage and gently press it
into place. Secure the T09 screws until they touch the module. This will engage the locking
tabs to hold it in place. Do not overtighten.
Note: If the T09 screws are not backed out first the module will not insert/remove
properly.
To remove the option module remove power from the VFD. Using a T09 driver bit back out
the option module 2 screws approximately 4 or 5 turns each. Gently pull the module out.