PACMotion VFD Syllabus
Section 8
GFK-3167B
December 2020
User Defined Function Block
–
Modbus/TCP (Note 5)
31
8.
Starting the system
Be sure to set your VFD Parameter P1-12 to 4 for Fieldbus Control.
Download the project to your PACSystems Controller.
Connect the top Ethernet Port of the CPE100 to the VFD Modbus/TCP option module. Power up the
devices and test functionality.
9.
Setting Fieldbus Connection Timeout Preferences
The VFD interface allows the user to set the Communication Loss Timeout and Communication Loss
Action values. These parameters are at addresses P5-05 and P5-06 respectively. The Timeout units
are 1 = 0.1 sec and the range is from 0.0 (disable) to 5.0 seconds. Set these appropriately. A setting of
0.0 seconds will allow the VFD to continue running if communications is lost.