G2-2 Series A-B 1771 Remote I/O 

Quick Start Manual

 

  

 

 

 

 

 

 

 

 

 

 

Page 1 

3835050 TDG22ABQS3-0 

    

1/07 

Subject to change without notice 

 

www.numatics.com/fieldbus

 

Getting Started

 

 

This is a brief document designed to quickly get you started setting up your valve manifold with an integrated 
Numatics’ G2-2 Series A-B 1771 Remote I/O communication node.  Please note that this document is not 
intended to replace the G2-2 Series A-B 1771 Remote I/O Technical Manual, which includes more detailed 
technical information.  The full technical manual can be found on the Numatics website at 

www.numatics.com

 or may be ordered by calling 248-887-4111. 

 

1) Initial Unpacking and Inspection 

 

1)

 

Examine exterior of package for signs of damage.  Report any damage to shipping carrier. 

 

2)

 

Remove wrapped manifold assembly from box. 
a)

 

Remove manifold assembly from anti-static packaging 

b)

 

Retain documentation for installation and configuration 

 

3)

 

Examine manifold assembly for any shipping damage such as: 
a)

 

Bent pins or connectors 

b)

 

Report any damage to shipping carrier immediately 

 

4)

 

Examine manifold assembly for proper ordered configuration. (Valves, I/O, Protocol, etc.)  

 

 2) G2-2 Introduction 

 

Below is an example of a 2012 series valve manifold.  This fieldbus manifold series is capable of addressing a 
total of 128 I/O (up to 1 full rack size).  The manifold can be viewed as having two sections to it, the 

Valve 

Side and the Discrete I/O Side.  The Valve Side supports a maximum of 32 solenoid coils and the Discrete 

I/O Side supports a maximum of 6 modules totaling 110 I/O.  The communication module has two 

connectors: a 5-pin communication connector and a 4-pin power connector.  Pin-outs for these, along with 
I/O connectors, and are labeled on the side of the respective modules. 

Valve

I/O Point

LED Status

Indicator(s)

Discrete I/O 

Connectors

Discrete I/O Side

(Maximum of 6 Modules)

Valve Side

(Maximum of 32 Solenoids)

Module/

Network

Status LED's

Chassis Ground 

Connection

Valve 

End Plates

Manual 

Override

Solenoid LED 

Status Indicator

Valve Side 

Sub-D Output 

Module

Communications 

Module (Node)

Manual Configuration 

Module (MCM)

Terminal Strip Module

8 Connector I/O Module

19 Pin Round 

Connector Module

COMM. STATUS

+24V VLV/OUT

+24V NODE/IN

FUSE 2

FUSE 1

A-B

1771 RIO

Dual 25 Pin Sub-D

w/Aux Power

Output Module

Содержание Numatics G2-2 series

Страница 1: ... immediately 4 Examine manifold assembly for proper ordered configuration Valves I O Protocol etc 2 G2 2 Introduction Below is an example of a 2012 series valve manifold This fieldbus manifold series is capable of addressing a total of 128 I O up to 1 full rack size The manifold can be viewed as having two sections to it the Valve Side and the Discrete I O Side The Valve Side supports a maximum of...

Страница 2: ...he user to manually set baud rate rack address and other user definable options The MCM consists of two DIP switch sets SW1 and SW2 and two rotary switches SW3 and SW4 MCM Module Part Numbers Description Part Number Complete Module 239 1384 Replacement Board 256 684 SW2 SW3 DIP Switch SW1 DIP Switch SW4 All DIP switches shown in the OFF position Rotary Switch Rotary Switch 1 4 3 2 5 6 7 8 ON 1 4 3...

Страница 3: ...t Hold Last State Switch Setting Description SW1 6 Off Reset Outputs SW1 6 On Hold Last State Starting Quarter SW1 7 SW1 8 Quarter Off Off 1st Off On 2nd On Off 3rd On On 4th DIP Switch Settings SW2 Valve Output Configuration Allocated Valve Coil Outputs SW2 6 SW2 7 SW2 8 Valve Coil Outputs Off Off Off 32 Coils Off Off On 24 Coils Off On Off 16 Coils Off On On 8 Coils On Off Off 0 Coils Any Other ...

Страница 4: ...tions 1 Disconnect power and air from the manifold 2 Record current MCM settings 3 Set the rotary switches to 99 SW3 and SW4 4 Make sure that SW1 5 SW2 1 and SW2 7 are in the ON position 5 Select the desired test mode with SW2 8 see table below Switch Testing Mode Setting Description Output Off Sequentially turns all the outputs ON and OFF SW2 8 Input Output On Causes all of the odd outputs to com...

Страница 5: ...lve Outputs 12 Word 0 Bits 0 11 Allocated Unused Valve Outputs 20 Word 0 Bits 12 15 Word 1 Bits 0 15 Discrete Outputs 24 Word 2 Bits 0 15 Word 3 Bits 0 7 Total Outputs 56 Inputs and Mapping Location Discrete Inputs 12 Word 0 Bits 0 3 8 15 Allocated and Reserved Inputs 4 Word 0 Bits 4 7 Total Inputs 16 Assumed Settings Single Z BoardsTM used with single solenoid valves Double Z BoardsTM used with d...

Страница 6: ...served Allocated Reserved Allocated Reserved Allocated Reserved 4 Discrete Output No 7 Discrete Output No 6 Discrete Output No 5 Discrete Output No 4 Discrete Output No 3 Discrete Output No 2 Discrete Output No 1 Discrete Output No 0 2 5 Discrete Output No 7 Discrete Output No 6 Discrete Output No 5 Discrete Output No 4 Discrete Output No 3 Discrete Output No 2 Discrete Output No 1 Discrete Output...

Страница 7: ...Load 1 No Fault 0 Sourcing PNP Discrete Outputs ON Fault Short Circuit Over Temp Over Current 1 7 Ground Wiring All Numatics Inc communication nodes should be grounded during the installation process These grounding guidelines can be found in National Electrical code IEC 60204 1 or EN 60204 1 There also is a ATTENTION CONNECT TO EARTH GROUND FOR PROPER GROUNDING OF UNIT label attached to the chass...

Страница 8: ...Outputs Valve Coils and Discrete Outputs 2 Earth Ground Protective Earth Case Ground 3 0VDC Common 0VDC Common for Valves I O and Node Power 4 24VDC Node and Inputs Voltage Used to Power Discrete Inputs and Node Electronics Maximum current capacity on the 0VDC common pin of the auxiliary power connector is 8 Amps The combined draw of the 24VDC Valves and Outputs and 24VDC Node and Inputs pins cann...

Страница 9: ...unication occurred when processor lockout is ON OFF Internal fuse F1 is OK valid only when power is applied to 24V VLV OUT pin on Aux Power connector FUSE 1 Red ON Internal fuse F1 is open No power is internally provided to valves or outputs Communication NOT affected OFF No DC Power present at 24V VLV OUT pin on Aux Power connector 24V VLV OUT Green ON DC Power applied to 24V VLV OUT pin on Aux P...

Страница 10: ...the Aux power connector Output Module Power Jumper SP Output module power supplied by 24VDC Valves and Outputs pin on the Aux power connector Valve Side Output Bytes 4 Bytes 32 Allocated Valve Coil Outputs Discrete I O Side I O Bytes Self Configuring based on the I O modules installed 11 Technical Support For technical support contact your local Numatics distributor If further information is requi...

Страница 11: ...e l îlot livré correspond à votre commande distributeurs E S protocole 2 Introduction à la série G2 2 Ci dessous un exemple représentant l ensemble d un îlot de distributeurs de la série 2012 Cette série d îlots à bus de terrain est capable d adresser un total de 128 E S jusqu à 1 taille de rack complète L îlot peut être considéré comme ayant deux parties la partie Composants pneumatiques et la pa...

Страница 12: ...isateur de configurer manuellement le taux baud l adresse du rack et les autres options définissables par l utilisateur Le MCM est équipé de deux ensembles de DIP switchs SW1 et SW2 et de deux roues codeuses SW3 et SW4 Codes des composants du module MCM Description Code Module complet 239 1384 Carte de rechange 256 684 SW2 SW3 DIP Switch SW1 DIP Switch SW4 All DIP switches shown in the OFF positio...

Страница 13: ... Switch Réglage Description SW1 6 Off Remise à l état initial des sorties SW1 6 On Maintien du dernier état Quarts de démarrage SW1 7 SW1 8 Quarts Off Off 1er Off On 2e On Off 3e On On 4e Réglages des DIP switchs SW2 Configuration des sorties électodistributeurs sorties des bobines électrodistributeurs allouées SW2 6 SW2 7 SW2 8 Sorties bobines d ED Off Off Off 32 bobines Off Off On 24 bobines Off...

Страница 14: ...tionnez les roués codeuses sur 99 SW3 et SW4 4 Assurez vous que les switchs SW1 5 SW2 1 et SW2 7 sont sur la position ON 5 Sélectionnez le mode test désiré à l aide du switch SW2 8 voir le tableau ci dessous Switch Mode test Réglage Description Sortie Off Les sorties sont successivement mises sous tension ON puis hors tension OFF SW2 8 Entrée Sortie On Les sorties impaires sont mises sous tension ...

Страница 15: ... 11 Sorties distr allouées non utilisées 20 Mot 0 Bits 12 15 Mot 1 Bits 0 15 Sorties discrètes 24 Mot 2 Bits 0 15 Mot 3 Bits 0 7 Nb total de sorties 56 Allocation entrées et mapping Entrées discrètes 12 Mot 0 Bits 0 3 8 15 Entrées allouées et réservées 4 Mot 0 Bits 4 7 Nb total d entrées 16 Réglages présumés Cartes Z BoardsTM simples utilisés avec les électrodistributeurs simples Cartes Z BoardsTM...

Страница 16: ...é Alloué et réservé Alloué et réservé Alloué et réservé Alloué et réservé Alloué et réservé 4 Sortie discrète 7 Sortie discrète 6 Sortie discrète 5 Sortie discrète 4 Sortie discrète 3 Sortie discrète 2 Sortie discrète 1 Sortie discrète 0 2 5 Sortie discrète 7 Sortie discrète 6 Sortie discrète 5 Sortie discrète 4 Sortie discrète 3 Sortie discrète 2 Sortie discrète 1 Sortie discrète 0 3 6 Sortie dis...

Страница 17: ... Sorties discrètes ON Défaut court circuit surchauffe surintensité de courant 1 7 Mise à la terre Tous les nœuds de communication de Numatics Inc doivent être mis à la terre pendant la procédure d installation Les exigences relatives à la mise à la terre sont fournies dans les normes CEI 60204 1 ou EN 60204 1 Une étiquette d avertissement ATTENTION RELIER L EQUIPEMENT A UNE PRISE DE TERRE POUR ASS...

Страница 18: ...tion des sorties Bobines d ED et sorties discrètes 2 Mise à la terre Mise à la terre mise à la terre de l enveloppe 3 0VCC Commun 0VCC commun pour distributeurs E S et alimentation du nœud 4 24VCC Nœud et entrées Tension utilisée pour l alimentation des entrées discrètes et l électronique du nœud La capacité maxi de courant sur la broche 0VCC commun du connecteur d alimentation auxiliaire est de 8...

Страница 19: ...eur OFF Fusible interne F1 est bon valide seulement dans le cas où la broche du connecteur d alimentation auxiliaire 24V VLV OUT est alimentée FUSE 1 Rouge ON Fusible interne F1 est ouvert pas d alimentation interne des distributeurs ni des sorties La communication N EST PAS affectée OFF Pas de courant CC présent sur la broche 24V VLV OUT du connecteur d alimentation auxiliaire 24V VLV OUT Vert ON...

Страница 20: ...Cavalier d alimentation du module de sortie SP Module de sortie alimenté par la broche 24VCC des distributeurs et sorties du connecteur d alimentation auxiliaire Octets de sortie de la partie composants pneumatiques 4 octets 32 sorties de bobines d ED allouées Partie électronique octets E S Auto configuration en fonction des modules E S installés 11 Support technique Pour le support technique cont...

Отзывы: