26 • MRLDS-250 Infrared Gas Detector I&O Manual
026-1315 Rev 4
7.5.
Input Status Flags
Input Status Flags are readable (using function code 02).
Table 7-3
- Input Status Flags
Reg
Description
Range
P.-##
3000
Alarm flag (0 or 1=Alarm)
0-1
- -
3001
Relay state (0 or 1=energized)
0-1
- -
3002
3003
Red LED state (0 or 1=ON)
0-1
- -
3004
Green LED state (0 or 1=powered
on)
0-1
- -
3005
Reserved
- -
3006
Start up (0=normal operation,
1=warming up)
0-1
- -
3007
Reserved
- -
3008
Reserved
- -
7.6.
Output Status Flags
Output Status Flags are readable (using function code 01) and writable (using function code 05).
Table 7-4
- Output Status Flags
Reg
Description
Range
P.-##
4000
Buzzer flag (0 or 1=ON)
0=Off
1=On
- -
4001
Test required (If operating for >1
year). (1=requires testing)
0=Okay
1=Test
- -
Detector fault (0 or 1=fault)
0-1
- -