Overview
Wiring and Configuration • 9
3
Wiring and
Configuration
3.1.
Overview
Prior to wiring and configuring the MRLDS-250,
ensure the following conditions have been met:
•MRLDS-250 backplate is mounted in an appropriate
location.
•The cover panel is removed.
•If the cover panel was reattached after mounting,
open the gas detector enclosure by pressing the top
latch with a suitable screwdriver or other flat blade.
With the top latch depressed pull the housing apart by
grasping the sides and pulling straight out. Align and
press together to close.
Figure 3-1
- Terminal Blocks and Cable Glands
NOTE: The pre-installed cable
gland (left) and the optional cable
on the gland (right) have a 1/4
cable capacity (each).
NOTE: Install the optional cable
gland in the right side of the base
unit if needed. Otherwise, install
the blanking plug that is included
in the mounting kit.
3.2.
Wiring Supply Power
(24VAC or 24VDC)
CAUTION: Incorrect wiring may
permanently damage the gas
detector and void the warranty.
Double check all terminations
before applying power.
Either 24VAC or 24VDC may be used to power the
MRLDS-250. Connect wiring to the appropriate
terminal locations (see
Table 3-1
. Use two wires,
between 14 and 22 AWG. Refer to
Figure 3-2
for (AC
wiring left) or DC wiring (right).
Figure 3-2
- Supply Power Wiring Options
Table 3-1
- Power Options and Terminal Block
Connections
Power
Option
Pin
Label
Wiring
Termination
24 VAC
1
L
24V AC line
2
N
24V AC
neutral
24 VDC
3
+
24V DC
positive
4
GND
24V DC
ground