Installation
9
4.3.2 Attaching Lower Liebert XDCF Module
Liebert XDCF modules mount on the rear of the Egenera BladeFrame cabinet, near the power mod-
ules. The cabinet and Liebert XDCF have prefabricated mounting holes and studs to ease mounting.
1. Set the lower Liebert XDCF module on the left side of the ledge on the rear of the Egenera
BladeFrame cabinet. Make sure the positioning stud on the bottom of the Liebert XDCF fits into
the locator hole on the ledge as shown in
Figure 8
.
Figure 8
Locator hole for lower unit stud
2. Press the Liebert XDCF against the Egenera BladeFrame cabinet.
3. Insert a panel fastener into the mounting bracket and screw it into the captive panel nut in the
rear of the Egenera BladeFrame cabinet. For the hole locations, see
Figure 6
. Tighten the
fasteners securely with a screwdriver, either a blade-type or Phillips.
4. Secure the Liebert XDCF to the cabinet by inserting and tightening four screws along the right
side of the Liebert XDCF (see
Figure 7
).
5. Press the front section of the top deflector against the Egenera cabinet and tighten the panel
fasteners joining the two-piece deflector.
NOTE
If a lower module and an upper module will be attached to the Egenera cabinet, proceed to
4.4 -
Attaching Upper Liebert XDCF Module
.