5.8
Protocols Folder—SNMP Subfolder
Folders and settings in this folder permit configuring the card for various types of SNMP
communication, including access, traps and other user settings.
SNMP Settings
• SNMPv3 Engine ID—The SNMPv3 engine ID; assigned automatically
• SNMP v1/v2c Enable—Enable or Disable SNMP v1/v2c
• SNMP v3 Enable—Enable or Disable SNMPv3
• Authentication Traps—An Authentication Trap is sent if an SNMP host tries to access the card
via SNMP, but either the host address is not in the SNMP Access Settings or it is using the wrong
Community String.
• Heartbeat Trap Interval—Enable or Disable and set interval 5 minutes, 30 minutes, 1 hour, 4
hours, 8 hours, 12 hours and 24 hours
• RFC-1628 MIB—Enable or Disable support for retrieval of data from the RFC-1628 MIB objects.
Required for proper operation of Liebert MultiLink
®
and applies only to managed UPS equipment
• RFC-1628 MIB Traps—Enable or Disable support for sending RFC-1628 traps. Required for
proper operation of Liebert MultiLink and applies only to managed UPS equipment
• Liebert Global Products (LGP) MIB—Enable or Disable support for getting and setting data using
the Liebert Global Products MIB.
• LGP MIB Traps—Enable or Disable support for Liebert Global Products MIB traps. LGP traps
will not be sent unless LGP MIB is enabled.
• LGP MIB System Notify Trap—Enable or Disable support for the LGP System Notification trap.
This is a single trap sent each time an alarm or warning is added or removed from the conditions
table. It provides a text description of the event in a varbind of the trap message. LGP System
Notify Traps will not be generated unless the LGP MIB is enabled.