background image

Installation

3

To put it in the system:
1. Connect the RJ-type connector to the Liebert iCOM 

control board at either the P66 or P67 connection if unit is 

equipped with a small display. If unit is equipped with a 

large display, connect the RJ-type connector to the CAN 

connector on the back of the large display.

2. Connect the MTA-style connector of the wire harness to 

TB102 of the Liebert iCOM-DO interface card.

Figure 2

ELV wiring for Liebert iCOM-DO

Connect 24VAC power 

from P45 on the fuse 

board to P43 on the 

unit control board

Connect CAN Bus to P66 or 

P67 on the back of Liebert 

iCOM control

Route CAN Bus communications from P999 

on the Liebert iCOM-DO board to P66 or P67 

on the back of the Liebert iCOM control

Route 24VAC 

power from P43 

on the cooling 

unit control board 

to TB100 on the 

Liebert iCOM-DO 

board

Liebert 

iCOM-DO 

board

Liebert Precision Cooling unit control board

 Fuse Board

Liebert 

iCOM 

control

Содержание Liebert ICOM-DO

Страница 1: ...Infrastructure Management Monitoring For Business Critical Continuity Liebert iCOM DO User Manual ...

Страница 2: ......

Страница 3: ...COM Controllers 2 3 0 CONFIGURATION 4 3 1 DIP Switch Settings 4 3 2 Diagnostic LEDs 4 3 3 Piezoelectric Horn 4 4 0 OUTPUTS STATUS AND ALARMS 5 FIGURES Figure 1 Typical system configuration 1 Figure 2 ELV wiring for Liebert iCOM DO 3 TABLES Figure 3 Typical system configuration 1 Figure 4 ELV wiring for Liebert iCOM DO 3 ...

Страница 4: ...ii ...

Страница 5: ...fications Electrical Requirements Voltage 24VAC or 24VDC 20 50 60 Hz Single Phase Power 10W maximum Environmental Conditions C F Operating Temp 5 to 55 41 to 131 Storage Temp 20 to 70 4 to 158 Humidity 10 to 95 RH non condensing Dimensions mm inches Card Only 178 x 102 x 38 7 0 x 4 0 x 1 5 Shipping 248 x 178 x 64 9 75 x 7 0 x 2 5 Weight kg lb Net 0 1 0 2 Shipping 0 6 1 3 Compatibility Precision Co...

Страница 6: ... supplied with the Liebert iCOM DO interface card P N 159084G1 is equipped with three connectors one at either end of the harness and one in the middle The harness taps power from the 24VAC input to the control board of the Liebert Precision Cooling unit To connect this power to the Liebert iCOM DO 1 Locate the connector containing the two red wires plugged into P43 on the control board and unplug...

Страница 7: ...ness to TB102 of the Liebert iCOM DO interface card Figure 2 ELV wiring for Liebert iCOM DO Connect 24VAC power from P45 on the fuse board to P43 on the unit control board Connect CAN Bus to P66 or P67 on the back of Liebert iCOM control Route CAN Bus communications from P999 on the Liebert iCOM DO board to P66 or P67 on the back of the Liebert iCOM control Route 24VAC power from P43 on the coolin...

Страница 8: ...ses the default address and will automatically detect the Liebert iCOM DO when it is con nected Refer to the Liebert iCOM manual for details 3 2 Diagnostic LEDs LEDs are provided on the interface card to provide informa tion for diagnostic purposes The following table summarizes their indications 3 3 Piezoelectric Horn The jumper P5 located adjacent to the piezoelectric buzzer is used to enable or...

Страница 9: ...r each alarm output is configurable For details refer to the Liebert iCOM manual SL 18835 available at Liebert s Web site www liebert com NOTE The top of the screw terminals cannot be used to obtain contact when using a meter to verify the status of a contact closure The meter must contact the terminal block in the openings where the wires are inserted Table 3 Standard mapping of status and alarms...

Страница 10: ...Outputs Status and Alarms 6 ...

Страница 11: ......

Страница 12: ...uare Building F Ortigas Jr Road Ortigas Center Pasig City 1605 Philippines 63 2 687 6615 Fax 63 2 730 9572 The global leader in enabling Business Critical Continuity AC Power Systems Connectivity DC Power Systems Racks Integrated Cabinets Embedded Computing Embedded Power Power Switching Control Precision Cooling Outside Plant EmersonNetworkPower com Services Surge Protection Technical Support Ser...