Communication System Manual
UPS System: HIPULSE E
(Modbus/Jbus Interface)
Description of Protocol
(04/07)
Page 5-15
5.10
EVENT HISTORY IN SELECTED BUFFER
This command may be used to read messages stored in the <Event-History> records.
Position
Meaning
Size (bytes) Values
Format
UPS MSS
40150
ALARM HOUR
2
0 : 23
ASCII
40151
ALARM MINUTES
2
0 : 59
ASCII
40152
ALARM SECONDS
2
0 : 59
ASCII
40153
ALARM DAY
2
1 : 31
ASCII
40154
ALARM MONTH
2
1 : 12
ASCII
40155
ALARM YEAR
2
00: 99
ASCII
40156
UPS status (ALARM)
2
HEX note 1
40157
Alarm status
2
Rotating
HEX note 2
40158
Alarm code
2
0 : 79
HEX
40159
Alarm 1- 16 (Alarm Hist)
2
-
HEX note 3
40160
Alarm 17- 32(Alarm Hist)
2
-
HEX note 3
40161
Alarm 33- 48(Alarm Hist)
2
-
HEX note 3
40162
Alarm 49- 64(Alarm Hist)
2
-
HEX note 3
40163
Alarm 65- 80(Alarm Hist)
2
-
HEX note 3
40164
Vout L1-L2(Alarm Hist)
2
1 Volt
HEX
40165
Vout L2-L3(Alarm Hist)
2
1 Volt
HEX
40166
Vout L3-L1(Alarm Hist)
2
1 Volt
HEX
40167
Vout L1-N(Alarm Hist)
2
1 Volt
HEX
40168
Vout L2-N(Alarm Hist)
2
1 Volt
HEX
40169
Vout L3-N(Alarm Hist)
2
1 Volt
HEX
40170
I out L1(Alarm Hist)
2
1 Ampere
HEX
40171
I out L2(Alarm Hist)
2
1 Ampere
HEX
40172
I out L3(Alarm Hist)
2
1 Ampere
HEX
40173
I out N(Alarm Hist)
2
1 Ampere
HEX
40174
Active Power L1(Alarm Hist)
2
1 kWatt
HEX note 4
40175
Active Power L2(Alarm Hist)
2
1 kWatt
HEX note 4
40176
Active Power L3(Alarm Hist)
2
1 kWatt
HEX note 4
40177
Bypass Freq. (Alarm Hist)
2
0.1 Hz
HEX note 4
40178
Inv. Freq. (Alarm Hist)
2
0.1 Hz
HEX note 4
40179
Vin L1-L2(Alarm Hist)
2
1 Volt
HEX
40180
Vin L2-L3(Alarm Hist)
2
1 Volt
HEX
40181
Vin L3-L1(Alarm Hist)
2
1 Volt
HEX
40182
V batt(Alarm Hist)
2
1 Volt
HEX note 5
---
40183
I batt(Alarm Hist)
2
1 Ampere
HEX note 4 e 5
---
40184
Apparent Power L1(Alarm Hist) 2
1 KVA
HEX
40185
Apparent Power L2(Alarm Hist) 2
1 KVA
HEX
40186
Apparent Power L3(Alarm Hist) 2
1 KVA
HEX
40187
Percent Load L1(Alarm Hist)
2
000:100 %
HEX
40188
Percent Load L2(Alarm Hist)
2
000:100 %
HEX
40189
Percent Load L3(Alarm Hist)
2
000:100 %
HEX
40190
Batt. Charge (Alarm Hist)
2
000:100 %
HEX note 4 e 5
---
40191
Batt.Time Remain (Alarm Hist)
2
Min.
HEX note 4 e 5
---
40192
Batt. Temp.(Alarm Hist)
2
0.1 °C
HEX note 4 e 5
---
5.10.1
Notes on ‘Selected Buffer Event History Request’
Note
UPS status:
bit 0 UPS Inverter status
0 = Inverter OFF
1 = Inverter ON
bit 1 UPS mains status
0 = Mains OFF
1 = Mains ON
bit 2 UPS rectifier status
0 = Rectifier OFF
1 = Rectifier ON
bit 3 UPS rectifier status
0 = Rectifier on buffer
1 = Rectifier manual
bit 4 UPS battery charge status
0 = Battery on load
1 = Battery charging
bit 5 UPS battery test status
0 = Battery test inactive
1 = Battery test in progress
bits 6 through 15 not in use