UPS System: HIPULSE E
Communication System Manual
Programming on Operator Panel
(Modbus/Jbus Interface)
Page 4-2
(04/07)
4.1.1
Selection of the JBUS/MODBUS Protocols from Operator Panel menu
•
Default window.
This message is displayed in the default window during normal UPS
operation; the message reads ‘ECOMODE’ if the UPS is a single module
configuration operating in EcoMode.
•
Information window.
Press ESC twice to display the UPS\MSS Logic board and Panel board
software release. This function is useful for upgrading software and finding
out exactly which functions are offered by the current version.
Press ESC again to return to the Default Window.
•
Main Menu window.
Press ENTER from the Default Window to go to the main menu.
Press DOWN to go to the FUNCTION line in the menu. Press ENTER to
confirm your selection and go to the selected sub-menu.
A request for the numerical password will appear. To enter the password, use
the UP key to scroll through values (0 through 9) for each digit, and press
DOWN to go on to the next digit. When you have finished entering the
password, press ENTER, and confirmation or an error message will appear.
For UPS
Select NEXT PAGE and press ENTER
For MSS
Select NEXT PAGE and press ENTER
For UPS
Select PROTOCOLS and press ENTER
For MSS
Select PROTOCOLS and press ENTER
The following procedures refer to setting of the JBUS Protocol. It should be noted that, in doing this, both MODBUS
and JBUS protocols are selected.
NORMAL OPERATION
HH.MM.SS DD.MM.YY
MEASUR/ALARM.HIST
>FUNCTION <
MAINTENANCE
SETUP
SW RELEASE
PANEL V xx.x
UPS LOGIC V xx.x
BATTERY TEST
IN/OUT BOARD
PANEL SETUP
>NEXT PAGE <
>PROTOCOLS <
ON/OFF UPS CONTROL
RELOAD UPS DATA
RESET/CONSTANT
WRITE SAVE
MOVE EXIT ESC
ENTER PASSWORD
>00000000<
SW RELEASE
PANEL V xx.x
MSS LOGIC V xx.x
IN/OUT BOARD
PANEL SETUP
>NEXT PAGE <
>PROTOCOLS <
ON/OFF MSS CONTROL
RELOAD MSS DATA
RESET BUFFERS