Chapter 3 Operation And Display Panel 23
Liebert GXT4 UPS 700VA ~ 3000VA (230V) User Manual
No. Prompt
Meanings
8
UPS shutdown process had been cancelled
The shutdown command sent through Multilink or SNMP card to the
UPS is cancelled
9
UPS reboot
Reboot the UPS through Multilink or SNMP card
10
UPS switch to Green mode
The UPS transfers back to Green mode, saving more electricity
11
UPS switch to Auto Green mode
When the input utility power satisfies the condition of Auto Green
mode, the UPS will transfer back to Auto Green mode
12
UPS switch to Online mode
The UPS transfers back to Online mode, supplying power to the
load through the inverter
13
UPS internal temperature return to normal
The internal temperature of the UPS recovers to normal range
14
UPS load return from overload
The loads are reduced, and the UPS recovers to normal state from
overload
15
UPS in OnLine operation
The UPS is operating in Online mode, supplying power to the load
through the inverter
16 Beeper
Disable
The beeper is disabled, and no audible alarm will be generated
when faults or warnings occur again
17 Beeper
Enable
The beeper is enabled, and audible alarms will be generated when
faults or warnings occur again
18
OUTLET1 Closed Auto / Manual
The programmable output receptacle 1 receives turn-off command
and is turned off
19
OUTLET1 Open Auto / Manual
The programmable output receptacle 1 receives turn-on command
and is turned on
20
OUTLET2 Closed Auto / Manual
The programmable output receptacle 2 receives turn-off command
and is turned off
21
OUTLET2 Open Auto / Manual
The programmable output receptacle 2 receives turn-on command
and is turned on
3.3.6 Warning List
All UPS warning messages are described in Table 3-4.
Table 3-4 Warning list
No. Warning
Description
1
Utility power not available
The utility power is not available, or it cannot satisfy the
requirements for the UPS to operate
2
UPS batteries low and exhausted soon
The battery capacity is low and will be exhausted soon
3
UPS has switched to battery mode
The utility power is abnormal or the PFC side is faulty, the UPS
transfers back to Battery mode
4
UPS SWITCH TO BYPASS
The UPS transfers back to Bypass mode, at this point, the input
utility power supplies power to the load directly, and the load is
not protected
5
UPS in Bypass operation
The UPS is operating in Bypass mode, at this point, the input
utility power supplies power to the load directly, and the load is
not protected
6
Start-up voltage Low
The start-up voltage is low
3.3.7 Fault List
All UPS fault messages are described in Table 3-5.
Table 3-5 Fault list
No. Fault
Description
1
UPS self test failed
The battery is bad or weak
2
UPS shutdown command received
The UPS shuts down through communication
3
UPS overload
The UPS is overloaded
4
Inverter Out of Order
The inverter is faulty
5
Battery Weak/Bad
The battery is bad or weak
6
Output Short-circuit
The output connection is short-circuited
7
DC Bus Over-voltage
The DC bus is faulty