Specifications and Technical Data
Liebert
®
e
XM
™
66
8.0
S
PECIFICATIONS
AND
T
ECHNICAL
D
ATA
8.1
Conformity and Standards
The Liebert
e
XM has been designed to conform to the following standards:
The Liebert
e
XM has UL and c-UL approval.
8.2
UPS Environmental
The Liebert
e
XM is designed to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Safety
UL 1778 4th Edition, CSA 22.2 107.3
Surge
IEC 61000-4-5 Criteria B
Harmonics
IEC 61000-3-4
Electrical Fast Transient
IEC 61000-4-4, Criteria B
ESD
IEC 61000-4-2, Criteria B
FCC
Part 15, Class A
Radiated Immunity
IEC 61000-4-3, Criteria A
Conducted Immunity
IEC 61000-4-6, Criteria A
Low-Frequency Signals
IEC 61000-2-2 Criteria A
Transportation
ISTA Procedure 1H
ISO
9001
Misc
OSHA, ASME, NEMA PE-1
Table 21
Environmental requirements
Item
Requirements
Acoustical Noise, dBA, at 55 in. (1.4m)
59
Operating Altitude
3281 ft. (1000m) 1% maximum kW derate per 328 ft. (100m) rise
between 3281 and 9843 ft. (1000m and 3000m)
Relative Humidity
95%
Operating Temperature, °F (°C)
104 (40)
UPS Storage/Transport Temperature, °F (°C)
-4 to 158 (-20 to 70)
Table 22
UPS mechanical characteristics
Rated Power, kVA
60 - 100
Dimensions, W x D x H, in (mm)
23-5/8 x 39-3/8 x 78-3/4 (600 x 1000 x 2000)
Weight, lb (kg)
955 (433)
Color
RAL 7021 (Black)
Protection Degree IEC (60529)
IP20