Installation
Liebert
®
e
XM
™
10
2.5
Mechanical Considerations
The Liebert
e
XM is constructed with a steel frame and removable panels. Top and side panels are
secured to the chassis by screws. The doors may be opened for access to power connection bars,
auxiliary terminal blocks and power switches.
The UPS comes with an Operator Control Panel that provides basic operational status and alarm
information. The cabinet houses the power components. Cooling is provided by internal fans. The unit
sits on four casters. Adjustable stops are provided to prevent the UPS from moving once it has been
moved to its final position.
2.5.1 Dimensions
Figure 1
UPS dimensions, center of gravity
!
WARNING
Risk of heavy units tipping over while being moved. Can cause property damage, injury and
death.
Emerson recommends lifting the units by installing four eyebolts in the factory-fabricated
holes, one at each corner of the unit, attaching cables or similar strapping to the eyebolts and
lifting with a suitable mechanism.
Table 1
Center of gravity and weights for Liebert
e
XM 60-100kVA frame
KVA Rating
Center of Gravity
Weight, lb (kg)
Dimension X
in. (mm)
Dimension Y
in. (mm)
Dimension Z
in. (mm)
Unit
Shipping
60
11.81 (300)
33.66 (855)
22.04 (560)
807 (366)
877 (398)
80
11.81 (300)
31.49 (800)
22.04 (560)
881 (400)
951 (431)
100
11.81 (300)
29.53 (750)
22.04 (560)
955 (433)
1025 (465)
39.5" (1000mm)
31.5"
(600mm)
Without Side Panels
Front
Front
Display
Vent Screen
Front and Back
Center
of Gravity
Center
of Gravity
78.7"
(2000mm)
1.56"
(40mm)
LEFT SIDE
FRONT
RIGHT SIDE
Overall
31.8
(808mm)
Dim. X
Dim. Z
See Pg. 2
See Pg. 2
Dim. Y
See Pg. 2
Refer to Table 1 for Dimensions X, Y and Z
in 60-kVA Liebert
e
XM models.