Operation
Liebert
®
e
XM
™
58
7.2.1 Startup Procedure
To start the UPS from a fully powered-down condition:
1. Open the external power switch.
2. Open the UPS door.
3. Connect the power supply cables.
4. Ensure the correct phase rotation.
5. Close the external input circuit breaker and connect input power.
The LCD activates. The rectifier indicator flashes while the rectifier is starting. The rectifier
enters normal operation state, and after about 30 seconds, the rectifier indicator stops blinking
and is illuminated in a steady green. After initialization, the bypass static switch turns on. The
mimic LEDs appear as shown
Table 18
.
6. Ensure that the Liebert Power Module assembly ready switches are latched (in Down position).
7. Close the external output circuit breaker.
8. Press the INVERTER ON button for 2 seconds. The inverter indicator flashes while the inverter
is starting. After the inverter is ready, the UPS transfers from bypass to inverter, the bypass
indicator turns Off, and the inverter indicator turns On. The UPS is in Normal Mode. The mimic
LEDs will appear as shown below.
9. Close the battery breaker.
Table 18
Mimic indicators after initialization
LED
Status
Rectifier Indicator
Green
Battery Indicator
Red
Bypass Indicator
Green
Inverter Indicator
Off
Load Indicator
Green
Status Indicator
Amber
Table 19
Mimic indicators for normal mode operation with battery breaker open
LED
Status
Rectifier Indicator
Green
Battery Indicator
Red
Bypass Indicator
Off
Inverter Indicator
Green
Load Indicator
Green
Status Indicator
Amber
Table 20
Mimic indicators for normal mode operation with battery breaker closed
LED
Status
Rectifier Indicator
Green
Battery Indicator
Off
Bypass Indicator
Off
Inverter Indicator
Green
Load Indicator
Green
Status Indicator
Green