Component Operation and Maintenance, Checks and Adjustments
63
Figure 12 Steam generating humidifier control board
7.6
Electric Reheat
Table 20
DIP switch settings for steam generating humidifier
Unit Rated
Voltage
Capacity
SW1
SW2
SW3
SW4
Rated Values
Voltage
AMP Set Pt
200/208
11
Off
On
Off
On
208
12.6
200/208
22
On
Off
On
On
208
23.8
230
11
Off
Off
Off
On
240
10.5
230
22
Off
Off
On
On
240
20.3
380/400/415
11
On
On
Off
Off
400
6.3
380/400/415
22
Off
On
On
On
400
12.6
460
11
On
Off
Off
Off
480
5.5
460
22
Off
Off
Off
On
480
10.5
575*
11
Off
Off
Off
Off
575
4.2
575*
22
Off
On
Off
On
575
9.8
*The values are only suitable in models FH600C and FH740C. All other models use a 575 volt to 460 volt step-down
transformer and therefore use the 460V settings.
!
CAUTION
Reheat element sheaths and fins are manufactured with stainless steel. Regular inspections
are necessary to assure proper cleanliness of the reheating element. Should inspection reveal
corrosion particles on the reheating element or adjoining surfaces (including ducts and
plenums), appropriate cleaning should be performed. Periodic reheating element replacement
may be required to meet specific application requirements.