Service Menu Parameters
85
Digital Scroll 2 NTC
—This parameter adjusts the digital scroll 1 NTC reading from the actual sen-
sor to compensate for any error or drift of the sensor.
Calibrated Digital Scroll 2 NTC
—This parameter shows the adjusted Digital Scroll 1 NTC sensor
value. This value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.
Figure 76 Sensor calibration / setup parameters - Page 2
Optional Sensor A, B & C
—This parameter adjusts the reading from the actual sensor to compen-
sate for any error of the sensor or to match other sensors in the room.
Calibrated Optional Sensor A, B & C
—This parameter shows the adjusted value of the sensor.
This value is the actual sensor reading (+ or -) the offset.
Optional Sensor B &C Type
—This parameter currently only supports the “TH” Temperature /
Humidity sensor type.
SENSOR CALIBRATION/SETUP (page 2 of 3)
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 3)
????
Optional Sensor A 1
+0°F
Calibrated Optional Sensor A 1
72°F
Optional Sensor A 2
+0.0 %
Calibrated Optional Sensor A 2
49.5 %
Optional Sensor B Type
TT
Optional Sensor B 1
+0°F
Calibrated Optional Sensor B 1
°F
Optional Sensor B 2
+0.0°F
Calibrated Optional Sensor B 2
°F
Optional Sensor C Type
TT
UNIT 01
S612
S613
S614
S615
S616
S617
S618
S619
S620
S621
S622