Service Menu Parameters
81
Type
—This selection sets the type of action for each event listed. There are 3 different types of events
(Alarm, Warning and Message). When an event is triggered and the type is set to alarm then the light
and buzzer on the Display will activate, an event will be written to the event log and the (K3) alarm
relay will close. If the type is set to Warning then the light and buzzer on the display will activate, an
event will be written to the event log and the (K3) alarm relay can be configured to close or provide no
reaction. If the type is set to Message, then the event is only written to the event log.
Figure 68 Set alarms parameters screen - Page 4
Figure 69 Set alarms parameters screen - Page 5
SET ALARMS (page 4 of 7)
PASSWORD (Actual Level 0)
????
DELAY
EN-DIS TYPE
COMP 1 OVERLOAD
ENABLE
ALM
COMP 2 OVERLOAD
ENABLE
ALM
COMP 1 HIGH PRESSURE
ENABLE
ALM
COMP 2 HIGH PRESSURE
ENABLE
ALM
COMP 1 LOW PRESSURE
ENABLE
ALM
COMP 2 LOW PRESSURE
ENABLE
ALM
COMP 1 PUMPDOWN FAIL
ENABLE
ALM
COMP 2 PUMPDOWN FAIL
ENABLE
ALM
DIGI SCROLL1 HIGH TEMP
ENABLE
ALM
DIGI SCROLL2 HIGH TEMP
ENABLE
ALM
EL HEAT HIGH TEMP
5 ENABLE WRN
S236
S237
S238
S239
S240
S241
S242
S243
S244
S245
S246
S247
S248
UNIT 01
SET ALARMS (page 5 of 7)
PASSWORD (Actual Level 0)
????
DELAY
EN-DIS TYPE
WORKING HRS EXCEEDED
0 ENABLE WRN
SMOKE DETECTED
2 ENABLE
ALM
WATER UNDER FLOOR
2 ENABLE
ALM
COND PUMP-HIGH WATER
2 ENABLE
ALM
LOSS OF FLOW
5 ENABLE
ALM
STBY PUMP ON
2 ENABLE
ALM
STANDBY UNIT ON
2 ENABLE
ALM
HUMIDIFIER PROBLEM
2 ENABLE
ALM
NO CONNECTION w/Unit1
ENABLE WRN
UNIT X DISCONNECTED
ENABLE WRN
LOSS OF POWER
DISAB WRN
S249
S250
S251
S252
S253
S254
S255
S256
S257
S258
S259
S260
S261
UNIT 01