Installation
37
Liebert
®
APS
™
Commissioning/Startup with AC Power Available (Normal Mode Operation)
___ 1. Verify that the upstream mains AC breaker is closed.
___ 2. Turn On the UPS Enable switch on the rear of the unit (it is protected by a clear plastic
cover).
___ 3. Close the UPS input breaker: it is on the front of transformer-free frame systems and on the
rear of transformer-based frame systems.
___ 4. Press the ON/OFF button on the LCD panel.
___ 5. When asked to confirm, press Enter (F5 button) to turn On the UPS.
___ 6. Close the UPS output breaker on the rear of the unit.
___ 7. If supplying power to an external distribution panel, close all breakers to provide power to the
equipment. If using the integral distribution PODs on the UPS or MBC, ensure the individual
POD breakers are closed.
Commissioning/Startup Without AC Power Available (Battery Mode Operation)
1. Check to ensure the upstream mains AC breaker is closed.
2. Turn on the UPS “Enable” switch on the rear of the unit.
3. Locate the “Battery Start” push button that is on either of the two control modules. Press and
hold this button for 5 seconds.
4. Close the output breaker on the rear of the Liebert APS.
5. If supplying power to an external distribution panel, close all breakers to provide power to the
equipment. If using the integral distribution PODs on the UPS or MBC, verify that the individual
POD breakers are closed.
6. Emerson recommends closing the UPS input breaker; it is on the front of transformer-free frame
systems and on the rear of transformer-based frame systems. If AC mains becomes available, the
UPS will revert to AC power mode and begin recharging the battery.
NOTE
This will begin the initial system checks and enable power to begin charging the battery
NOTE
Starting the UPS system without AC power will discharge the batteries. If AC mains power is
not restored before the batteries discharge, the USP will shutdown and power will be lost to the
connected equipment. If the UPS reaches the battery EOD level and shuts down, AC mains
power must be present to restart the UPS system.
NOTE
This will begin the initial system checks and automatically enable output power.