Installation
Liebert
®
APS
™
22
2.4
Module Installation
The Liebert APS ships from the factory configured (modules prepopulated) and tested as a system to
the customer’s requirements. If any modules were removed to facilitate ease of installation, follow the
steps below to re-insert them properly.
2.4.1
Installing Power Module, Battery Module and Charger Module
1. Lift module to appropriate bay, resting end of module on bay shelf.
2. Push the module into the bay slowly. The module will be locked until 1/3 is in.
a. At this point, lift the module up and continue pushing it until about 5cm of the module is still
out of the bay.
b. Push it firmly and smoothly to ensure that the module is fully inserted, as shown in
Figure 26
.
Figure 26 Insert the power module, battery module and charger module
3. Use a #2 Phillips screwdriver to install the module-securing bracket, and then press the lever
down into the bracket, as shown in
Figure 27
.
NOTE
Use caution not to rest the module on any of the plastic bezels, this could damage the bezel.
Two battery modules must be installed in the same row to complete the battery string.
50mm
Step 2 a
Step 1
Step 2 b