• Air or non-condensable gas in syste
• Recover refrigerant, evacuate and recharge
Suction &
Discharge pressure
balanced
• Compressor may loss pumping
• If Cooling achieve, Gauges may faulty
• Compressor may trip on IPRV
• Replace
• Gauges Replace
• Check for high side restriction in the system
Unit /Compressor
Draw high Amps
•Run or start capacitor defective
•Start relay defective
•Loose wire
•Low Voltage or Voltage Fluctuation
•Moisture in the system
•Liquid Flood back in the compressor
•Any Contamination/ Oil Dilute
• Replace
• Replace
• Check for correct voltage at compressor – check
and tighten all connections
• Recover refrigerant – evacuate and recharge
• replace filter drier
• Ensure proper load
• Check oil quality, replace with new oil & do the
commissioning as per procedure
Compressor trip on
IOLP
• Leakage in the System
• Compressor Stuck/JAM
• Compressor getting hot & Motor temperature
Shooting – up
• Reverse rotation of compressor
• Repair
• Replace
• Maintain proper suction superheat & check oil
level/return to compressor
• Check voltage & connection of Comp. terminal
22