7
•
Refer Table 3, for the
Electrical details of the KHZXXXLRL CDU models as under
Table 3:
Electrical data for the
KHZXXXLRL
CDUs
Model
Compressor
Rated Voltage
CDU MCC
(A)
Contactor
Rating
Cu. Cable Size
ZSI06KQE-TFM
380-420V/50 Hz/3Ph
7.9
9A
2.5 Sq. mm
ZSI08KQE-TFM
380-420V/50 Hz/3Ph
7.9
9A
2.5 Sq. mm
ZSI09KQE-TFM
380-420V/50 Hz/3Ph
7.8
9A
2.5 Sq. mm
ZSI11KQE-TFM
380-420V/50 Hz/3Ph
11.2
12A
2.5 Sq. mm
ZSI14KQE-TFM
380-420V/50 Hz/3Ph
12.1
12A
2.5 Sq. mm
ZSI15KQE-TFM
380-420V/50 Hz/3Ph
12.7
18A
2.5 Sq. mm
ZSI18KQE-TFM
380-420V/50 Hz/3Ph
15
22A
4.0 Sq. mm
ZSI21KQE-TFM
380-420V/50 Hz/3Ph
19.3
22A
4.0 Sq. mm
•
Always use AC-3 Category Contactor with above mentioned rating in table
.
•
Refer below the operating envelope of the KHZXXXLRL CDU models
Figure
4 : Operating Envelope f or KHZXXXLRL Models
Refrigerant R404A; Suction return gas temperature: 5° C
KHZ506LRL-E5EC6C
KHZ508LRL-E5EC6C
KHZ509LRL-E5EC6C
KHZ511LRL-E5EC6C
KHZ514LRL-E5EC6C
KHZ515LRL-E5EC6C
KHZ518LRL-E5EC6C
KHZ521LRL-E5EC6C