Electronic Bypass Controller Installation and Commissioning Guide
37
Start-Up Checklist – Variable Frequency Drive
Date (dd/mm/yyyy):
Emerson Order #:
YES
NO Power On LED illuminated
YES
NO Motor rotation in VFD Mode is correct
YES
NO Motor rotation in Bypass Mode is correct
YES
NO Motor rotation same in VFD and Bypass (
Motor rotation must be correct or damage can occur!
)
YES
NO Automatic controls functional
YES
NO Unit ready for startup with all connections made and control interface, power and load available?
YES
NO Enclosure inspected for shipping damage, physical integrity; door, latch and lock operation?
YES
NO Line and motor power connections tight and made to proper terminals with satisfactory clearances?
YES
NO Control wiring present and made to proper terminals and pull apart terminal blocks fully engaged?
YES
NO Physical installation and wiring conform to factory drawings or manuals as required?
YES
NO Control devices, contactors, overloads, breakers, switches, operating mechanisms, interlocks, OK?
YES
NO Separate AC line reactor, dc link reactor, or dynamic brake module/resistor, if supplied, properly installed?
YES
NO
Basic settings, application specific settings, and purchased options setup completed?
YES
NO Line voltage and current Motor nameplate
YES
NO After all parameters are set, save them by entering “1000” at parameter X.00 and hit “Off/Reset”
YES
NO
Save parameters to SmartCard by entering “Prog” at parameter 0.030 and
hit “Off/Reset”
Line Voltage & Current
Motor Nameplate
V
L12
:
V
L23
:
V
L31
:
Hp:
FLA:
PF:
I
L1
:
I
L2
:
I
L3
:
RPM:
LR Code:
Eff:
Parameters changed from factory default and new value:
Par
Value
Par
Value
Par
Value
Comms Address:
Comments:
Start-up Checklist completed by:
Date (dd/mm/yyyy):
7.4 Startup Checklist – VFD