Electronic Bypass Controller Installation and Commissioning Guide
31
5.2 Recommended Programming
Following is a list of parameters that should be programmed at the time of start-up.
These values are recommendations only, actual settings should be determined by the
application requirements, conditions, and the policies of the equipment owners. Refer
to the respective drive User Guide for a full parameter list and explanation.
Parameter
Menu 0
Equivalent
Description
Setting
Units
Fan
Pump
01.006
00.011
Max. Speed Hz
60
60
Hz
01.007
00.010
Min Speed Hz
15
6
Hz
02.011
00.012
Acceleration rate 1
100
16.6
s/100 Hz
02.021
00.013
Deceleration rate 1
100
16.6
s/100 Hz
05.007
00.020
Motor rated current
From Motor
A
05.008
00.019
Motor load rpm/rated speed
From Motor
RPM
05.009
00.018
Motor rated voltage
From Motor
V
05.013
00.015
Dynamic V/ F flux optimize select
OFF
OFF
-
06.009
00.023
Catch a spinning motor
1
1
-
07.019
-
Analog output 1 source
05.001 05.001 menu.param
08.011
Digital I/O 01
1
1
Invert
08.021
-
Digital I/0 01 Source Destination 10.001 10.001
Drive OK
11.044
00.031
Security status
(1)
(1)
-