22
Parameter
Menu 0
Equivalent Description
Setting
Units
Fan
Pump
1.06
0.02
Maximum set
speed
60.0 60.0 Hz
1.07
0.01
Minimum set
speed
15.0 6.0
Hz
2.11
0.03
Acceleration rate
1
100.0 16.6 s/100 Hz
2.21
0.04
Deceleration rate
1
100.0 16.6
s/100
Hz
5.07
0.46
Motor rated
current
From Motor
A
5.08
0.45
Motor load
rpm/rated speed
From Motor
RPM
5.09
0.44
Motor rated
voltage
From Motor
V
5.13
0.09
Dynamic V/ F flux
optimise select
OFF OFF -
6.09
0.33
Catch a spinning
motor
1
1
-
7.19
-
T9 analog output 1
source
5.01 5.01 menu.param
7.33
-
T9 analog output 1
control
Adv Adv -
8.21
-
T24 digital I/O
source/destination
10.02 10.02 menu.param
11.44
0.49
Security status
L2
L2
-
Note: If the analog speed reference into VFD terminal 7 is 0–10 Vdc instead of
the default 4–20 mA, parameter 7.11 (menu 0 parameter 0.19) must be
changed to VOLt (4).