Parameter
Menu 0
Equivalent
Description
Setting
Units
1.51
27
Power-up keypad reference
LASt
-
2.04
30
Ramp mode select
FASt
-
2.06
-
S ramp enable
On
-
2.07
-
S ramp acceleration limit
60
s/100 Hz
5.14
41
Voltage mode select
Fd
-
6.12
-
Enable stop key
On
-
7.06
16
Analog input 1 mode (terminal T2)
4-.20
-
8.22
-
Terminal B4 digital input destination 6.39
menu.param
8.23
-
Terminal B5 digital input destination 6.30
menu.param
8.24
-
Terminal B6 digital input destination 10.33
menu.param
8.25
-
Terminal B7 digital input destination 0.00
menu.param
9.04
-
Logic function 1 source 1
8.03
menu.param
9.06
-
Logic function 1 source 2
8.05
menu.param
9.10
-
Logic function 1 destination
1.43
menu.param
6.40
-
Enable sequencer latching
Off
-
4.2 Affinity BA Required Programming
The following
Affinity BA
parameters must be set to the values shown in order
to ensure proper operation of the Electronic bypass package. These settings
are pre-programmed from the factory,
DO NOT change any of these values unless directed to by Emerson
Control Techniques technical support. Note these parameters must be
programmed in the sequence shown.
Parameter
Menu 0
Equivalent
Description
Setting
Units
Fan
Pump
1.14
0.05
Reference selector
A1.A2
A1.A2 -
1.51
-
Power-up keypad reference
LASt
LASt
-
1.52
-
Enable hand/off/auto keypad mode
1
1
2.06
-
S ramp enable
On
On
-
2.07
-
S ramp acceleration limit
60
10
s/100 Hz
6.12
-
Enable stop key
On
On
-
6.49
-
Disable multi-mode drive module, no
storing on trip
On
On
-
7.10
-
T5/6 analog input 1 destination
0.00
0.00
menu.param
7.14
0.20
T7 analog input 2 destination
1.36
1.36
menu.param
Содержание FPCBA
Страница 7: ...1 VFD Labels Typical Standard VFD Rating Label Typical VFD Approvals Label ...
Страница 8: ...2 2 3 Part Number Identification ...
Страница 40: ...34 Chapter 8 8 1 FPCSK Schematic ...
Страница 41: ...35 8 2 FPCBA Schematic ...
Страница 42: ...36 NOTES ...
Страница 43: ...37 Part Number 027 2201 Issue 1 1 Control Techniques Americas LLC 2009 ...