![Emerson FloBoss S600 Скачать руководство пользователя страница 86](http://html.mh-extra.com/html/emerson/floboss-s600/floboss-s600_instruction-manual_102566086.webp)
S600 Instruction Manual
7-6 Startup
Revised
Jan-07
Message Meaning
CONFIGURING
PLEASE WAIT.
S600 is attempting a cold or warm start.
INSUFFICIENT
MEMORY
Cannot complete a cold start due to
insufficient S600 memory.
To resolve:
Reduce the report/alarm/event
history.
HARDWARE DOES
NOT SUPPORT
MULTI-STREAM
APPLICATIONS
This S600 supports only a single stream.
To resolve:
Contact your support centre
for further directions.
REPORT CONFIG
HAS CHANGED
COLD START
REQUIRED
This normally occurs when the report
layout has been changed.
To resolve:
Initiate a cold start on the
S600 or download the original config (prior
to report changes).
ERROR LOADING
REPORT TEMPLATES
S600 has encountered an error when
reading the report templates.
To resolve:
Check reports for errors. If
you don’t find errors, contact your service
centre.
SYSTEM IS BEING
CONFIGURED
EXTERNALLY
PLEASE WAIT.
A configuration file is being downloaded to
the S600.
SYSTEM
RESTARTING
PLEASE WAIT.
A reboot is in progress.
Содержание FloBoss S600