![Emerson FloBoss S600 Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/emerson/floboss-s600/floboss-s600_instruction-manual_102566053.webp)
S600 Instruction Manual
Note
:
The return lines (such as pin 17 on SKT-E) must be connected to
a 24 Volts dc source. The DIGIN lines (such as pin 13 on SKT-E)
expect typical “open collector” (referenced to GND) connections.
Refer to Figures 4-23 and 4-24 for field wiring schematics.
Figure 4-23. Digital Input Schematic (Open Collector Device)
Figure 4-24. Digital Input Schematic (Relay)
Table 4-15. DIGIN Pin Connections for SKT-E
Pin Function
13 DIGIN-CH1
14 DIGIN-CH2
15 DIGIN-CH3
16 DIGIN-CH4
17 RETURN
CH1-4
18 DIGIN-CH5
19 DIGIN-CH6
1 DIGIN
CH-17
2 DIGIN
CH-18
3 DIGIN
CH-19
4 DIGIN
CH-20
5 RETURN
CH-17-20
6 DIGIN
CH-21
7 DIGIN
CH-22
8 DIGIN
CH-23
9 DIGIN
CH-24
10
RETURN CH 21-24
20 DIGIN
CH-25
21 DIGIN
CH-26
22 DIGIN
CH-27
23 DIGIN
CH-28
24
RETURN CH 25-28
25 DIGIN
CH-29
Revised Jan-07
I/O