limit of the control pressure range or 

that particular spring (see Specifications 

section). if the desired control pressure 

is not within the range of the control 

spring, install a spring of the proper 

range according to the Diaphragm 

and Spring case area section of the 

Maintenance procedure.

With installation completed, the regulator can be 

placed in operation by slowly opening the upstream 

and downstream block valves, if used, while using 

gauges to monitor pressure. The regulator takes 

control when downstream pressure is established.
The regulator has been adjusted at the factory to 

provide approximately the control pressure requested. 

To ensure the correct pressure setting always use a 

pressure gauge to verify the pressure setting. The 

range of allowable pressure settings is stamped on the 

spring casing nameplate. If a pressure setting beyond 

the stamped range is required, install a spring with the 

desired range by following the procedures for changing 

the spring and diaphragm in the Maintenance section. 

To adjust the pressure setting, perform the following 

steps (key numbers are referenced in Figure 6):

 

1. Remove the closing cap (key 3, if required).

  2.  Turn the adjusting screw (key 2) either clockwise 

to increase control pressure or counterclockwise 

to decrease control pressure. The regulator will 

go into immediate operation. To ensure correct 

operation always use a pressure gauge to monitor 

the blanket pressure when making adjustments.

  3. Replace the closing cap (key 3, if required).

Shutdown

Installation arrangements vary, but in any installation 

it is important to open and close valves slowly and 

to close the upstream block valve first when shutting 

down the system.
First, close the nearest upstream block valve and 

then, close the nearest downstream block valve to 

vent the regulator properly. Next, open the vent valve 

between the regulator and the downstream block valve 

nearest to it. Then, open the upstream vent valve and 

the vent valve in the control line. All pressure between 

these block valves is released through the open vent 

valves, since a gas blanketing regulator remains open 

in response to the decreasing downstream pressure. 

If vent valves are not installed, safely bleed off both 

inlet and outlet pressures and check that the regulator 

contains no pressure.

Maintenance

Regulator parts are subject to normal wear and 

must be inspected and replaced as necessary. The 

frequency of inspection and replacement of parts 

depends upon the severity of service conditions 

or the requirements of local, state and federal 

regulations. Due to care Emerson takes in meeting 

all manufacturing requirements (heat treating, 

dimensional tolerances, etc.), use only replacement 

parts manufactured or furnished by Emerson.

!

WaRninG

To avoid personal injury, property damage 

or equipment damage caused by sudden 

release of pressure, isolate the regulator 

from all pressure and cautiously release 

trapped pressure from the regulator 

before attempting disassembly.

Key numbers are referenced in Figure 6.

Body area

This procedure is for gaining access to the disk 

assembly, orifice, body gasket, split ring and pitot tube if 

used. All pressure must be released from the regulator, 

before these steps can be performed.
  1.  Unscrew the union nut (key 19) from the body 

(key 28) and remove the lower casing assembly 

(key 20) and split ring (key 17). The lower casing 

assembly (key 20) must be tipped toward the 

body outlet to allow removal clearance for the 

pitot tube (key 74).

  2.  Inspect and replace the orifice (key 27) 

if necessary. Lubricate the threads of the 

replacement orifice with a good grade of pipe 

thread sealant. Install the orifice with 75 to 

100 ft-lbs / 102 to 136 N•m of torque.

  3.  Remove the cotter pin (key 14) if it is necessary to 

replace the disk assembly (key 25).

  4.  To replace the pitot tube (key 74) on units with 

internal pressure registration, remove the flared 

end connection and press a new pitot tube into 

the pitot tube hole and secure by flaring the end. 

Rotate the pitot tube so that it points into the 

outlet of the body (key 28) after the lower casing 

assembly (key 20) is installed.

5

Type Y692

Содержание Fisher Y692

Страница 1: ...he Manual This instruction manual provides installation startup maintenance and parts ordering information for the Type Y692 Low Pressure Gas Blanketing Regulator Product Description The Accu Pressure Type Y692 Gas Blanketing Regulator Figure 1 is a pressure reducing direct operated regulator with internal registration or external pressure registration It is used for accurate pressure control on v...

Страница 2: ...stallation with spring case pointing up will change outlet control pressure range to 7 5 in w c to 1 3 psig 19 to 90 mbar Table 1 Control Pressure Ranges Available Configurations Direct operated pressure reducing regulator with external or internal pressure registration with seven outlet control pressure ranges from 1 in w c to 7 psig 2 mbar to 0 48 bar Available in NPS 1 1 2 and 2 DN 40 and 50 bo...

Страница 3: ...rd GAS BLANKETING PRESSURE Liquid INLET PRESSURE control PRESSURE ATMOSPHERIC PRESSURE INLET PRESSURE OUTLET PRESSURE ATMOSPHERIC PRESSURE Figure 3 Type Y692 with External Registration Operational Schematic block valve supply pressure vent valve vent valve vent pointed downward block valve Liquid gas blanketing pressure When the liquid level drops and vessel pressure decreases below the setting of...

Страница 4: ...ction are shown in Figure 6 Warning If the regulator vents some gas or a leak develops in the system it indicates that service is required Failure to take the regulator out of service immediately may create a hazardous condition In hazardous or flammable gas service vented gas may accumulate and cause personal injury death or property damage due to fire or explosion Vent a regulator in hazardous g...

Страница 5: ...ent valve in the control line All pressure between these block valves is released through the open vent valves since a gas blanketing regulator remains open in response to the decreasing downstream pressure If vent valves are not installed safely bleed off both inlet and outlet pressures and check that the regulator contains no pressure Maintenance Regulator parts are subject to normal wear and mu...

Страница 6: ...crews key 21 and spring case key 23 3 In a regulator with a light control spring see Figure 4 Lift the upper spring seat key 44 lower spring seat key 4 and control spring key 1 off the diaphragm and plate assembly key 5 In a regulator with a heavy control spring see Figure 5 Lift the two spring seats key 4 and control spring key 1 off the diaphragm and plate assembly key 5 4 Remove the diaphragm a...

Страница 7: ...ard MR0175 and or MR0103 Type Y692 Regulator Figure 6 Key Description Part Number Type Y692 Parts Kit For 1 4 3 8 and 1 2 in 6 4 9 5 and 13 mm Orifice Sizes includes keys 5 7 14 16 25 and 35 RY692X00012 For 3 4 1 and 1 3 16 in 19 25 and 30 mm Orifice Sizes includes keys 5 7 14 16 25 35 46 and 47 RY692X00022 1 Control Spring Plated steel See Table 1 2 Adjusting Screw See Table 4 3 Closing Cap See T...

Страница 8: ...0825X0012 1 2 in 13 mm 0L0401X0012 3 4 in 19 mm 1A8323X0012 1 in 25 mm 1A8324X0012 1 3 16 in 30 mm 1C7834X0012 28 Body NPT Cast iron NPS 1 1 2 in DN 40 size 1B403619012 NPS 2 in DN 50 size 1B403719012 Key Description Part Number 28 Body continued Steel NPS 1 1 2 in DN 40 size 2L244522012 NPS 2 in DN 50 size 2L243322012 Stainless steel NPS 1 1 2 in DN 40 size 2L244533092 NPS 2 in DN 50 size 2L2433X...

Страница 9: ...12 Aluminum 1A500528982 Plated steel 1A500528982 Plated steel 3 Closing Cap 1A589544022 Steel 1J8801X0022 Stainless steel 1H798714012 Brass 1J8801X0022 Stainless steel 4 Lower Spring Seat 14B4240X012 Aluminum 14B4240X012 Aluminum 1H7974X0012 Plated steel 1H7974X0012 Plated steel 29 Pipe Plug 1C333528992 Steel 1C3335X0012 Stainless steel 1C333528992 Steel 1C3335X0012 Stainless steel 30 Cap Screw 1B...

Страница 10: ... Internal registration APPLY LUBricant SEALant ADHesive 43B0674 B TYPE ORIFICE SPRING RANGE DATE MFGD FISHER CONTROLS CO MARSHALLTOWN IOWA USA 21 22 44 35 30 23 74 47 29 50 51 13 20 11 19 17 16 14 25 27 46 28 6 5 4 3 2 1 7 8 9 10 Type Y692 ...

Страница 11: ...n Figure 6 Type Y692 Regulator Assembly continued Section a a TYPE ORIFICE SPRING RANGE DATE MFGD FISHER CONTROLS CO MARSHALLTOWN IOWA USA 30 23 47 29 50 51 56 71 14 25 27 46 28 a a 21 22 20 13 19 16 35 30 23 15 47 14 28 25 27 46 17 11 6 5 4 3 2 1 7 9 8 11 Type Y692 ...

Страница 12: ...arantees express or implied regarding the products or services described herein or their use or applicability All sales are governed by our terms and conditions which are available on request We reserve the right to modify or improve the designs or specifications of our products at any time without notice Emerson Process Management Regulator Technologies Inc does not assume responsibility for the ...

Отзывы: