2

Type SR5 

Installation 

Only qualified personnel should install or 

service a regulator.  regulators should 

be installed, operated, and maintained 

in accordance with international and 

applicable codes and regulations, and 

Fisher instructions. 

If the regulator vents fluid or a leak 

develops in the system, it indicates that 

service is required. Failure to take the 

regulator out of service immediately may 

create a hazardous condition. 
Personal injury, equipment damage, or 

leakage due to escaping fluid or bursting of 

pressure-containing parts may result if this 

regulator is overpressured or is installed 

where service conditions could exceed the 

limits given in the Specifications section, 

or where conditions exceed any ratings of 

the adjacent piping or piping connections. 
to avoid such injury or damage, provide 

pressure-relieving or pressure-limiting 

devices (as required by the appropriate 

code, regulation, or standard) to prevent 

service conditions from exceeding limits. 
additionally, physical damage to the 

regulator could result in personal injury 

and property damage due to escaping 

fluid. To avoid such injury and damage, 

install the regulator in a safe location. 

Clean out all pipelines before installation of the regulator 

and check to be sure the regulator has not been damaged 

or has collected foreign material during shipping.  Use 

suitable line gaskets and approved piping and bolting 

practices.  Install the regulator in any position desired.  

However, to ensure self-draining (from outlet to inlet) the 

regulator should be installed with the spring case in the 

upright vertical position.  The arrow on the body indicates 

flow direction.

Note 

It is important that the regulator be 

installed so that the vent hole in the 

spring case is unobstructed at all times. 

overpressure Protection 

The recommended pressure limitations are stamped 

on the regulator nameplate. Some type of overpressure 

protection is needed if the actual inlet pressure 

exceeds the maximum operating outlet pressure rating. 

Overpressure protection should also be provided if the 

regulator inlet pressure is greater than the safe working 

pressure of the downstream equipment. 

Regulator operation below the maximum pressure 

limitations does not preclude the possibility of damage 

from external sources or debris in the line. The 

regulator should be inspected for damage after any 

overpressure condition. 

Startup

The regulator is factory set at approximately the 

midpoint of the spring range or the pressure requested, 

so an initial adjustment may be required to give the 

desired results.  

Make sure the CIP/SIP Pin (key 30, 

Figure 1) is not installed in the spring case.  

With 

proper installation completed and relief valves properly 

adjusted, slowly open the upstream and downstream 

shutoff valves.

the CIP/SIP pin must be removed before 

regulator is placed in operation. the 

pin will inhibit the proper operation and 

function of the regulator and result in 

overpressure of the downstream system.

adjustment

 

To change the outlet pressure, remove the closing cap 

or loosen the locknut and turn the adjusting screw or 

handwheel clockwise to increase outlet pressure or 

counterclockwise to decrease pressure. Monitor the outlet 

pressure with a test gauge during the adjustment. Replace 

the closing cap or tighten the locknut to maintain the 

desired setting.

Pressure loaded Construction

The spring case can be pressure loaded to adjust outlet 

pressure. An optional tapped spring case, guide ring seal 

and sealing washer on the adjusting screw must be used 

for these applications. The loading pressure is connected 

to the 1/4-inch NPT connection in the spring case 

allowing registration on the spring side of the diaphragm. 

Adjusting loading pressure will proportionally change the 

outlet pressure setting of the regulator. A small amount of 

mechanical spring load, in addition to the pressure load, is 

recommended. Regulator set pressure achieved from the 

combination of spring load and pressure load should not 

exceed the outlet pressure ranges listed on page 1.

Taking Out of Service (Shutdown)

 

to avoid personal injury resulting from 

sudden release of pressure, isolate 

the regulator from all pressure  before 

attempting disassembly.  relieve all spring 

compression and isolate regulator from the 

pressurized system prior to removing the 

clamp (key 15, Figure 1).

Содержание Fisher SR5

Страница 1: ...Maximum Inlet Pressure 14 5 bar at 65 C 210 psig at 150 F 12 4 bar at 135 C 180 psig at 275 F 11 bar at 204 C 160 psig at 400 F Maximum Outlet Pressure 10 3 bar at 65 C 150 psig at 150 F 8 62 bar at 135 C 125 psig at 275 F 7 58 bar at 204 C 110 psig at 400 F Proof Test Pressure All Pressure Retaining Components have been proof tested per Directive 97 23 EC Annex 1 Section 7 4 Outlet Pressure Range...

Страница 2: ...or inlet pressure is greater than the safe working pressure of the downstream equipment Regulator operation below the maximum pressure limitations does not preclude the possibility of damage from external sources or debris in the line The regulator should be inspected for damage after any overpressure condition Startup The regulator is factory set at approximately the midpoint of the spring range ...

Страница 3: ...escription 1 Body 2 Plug metal seat 3 Plug O Ring 4 Diaphragm Plate O Ring 5 Piston Ring 6 Diaphragm Gasket 7 Diaphragm 8 Lower Spring Seat 9 Guide Ring 10 Diaphragm Plate 11 Upper Spring Seat 12 Spring 13 Inner Spring 14 Spring Case 15 Bolted Clamp 16 Hex Nut 17 Hex Nut 18 Adjusting Screw 19 Closing Cap 22 Locking Lever 23 Flat Washer 24 Lock Washer 26 Upper Plug 27 Lower Plug 28 Soft Seat 30 Rin...

Страница 4: ...ility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Process Management product remains solely with the purchaser Fisher Controls International Inc 2004 2006 All Rights Reserved Industrial USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5856 Outside U S 1 469 293 4201 Asia Pacific Shanghai China 201206 Tel 86 21 58...

Отзывы: