HSRL Series

regulators depends upon the severity of 

service conditions or the requirements of 

local, state, and federal regulations.  Even 

under ideal conditions, these regulators 

should be replaced after 20 years from 

date of manufacture or sooner should 

inspection reveal the need.

Visually inspect the regulator each time a gas delivery 

is made for:

• 

Improper installation, vent not pointed vertically 

down or under a cover; no vent tube on 

underground systems

• 

Plugged or frozen vent

• 

Wrong regulator or no regulator in the system

• 

Internal or external corrosion

• 

Flooded Regulator; water in spring case; regulator 

submersed on underground tanks 

• 

Regulator age

• 

Any other condition that could cause the 

uncontrolled escape of gas

Failure to properly inspect the regulator could result in 

personal injury or property damage.

vent Opening

Make sure the regulator vent, vent assembly, or vent 

tube does not become plugged by mud, insects, ice, 

snow, paint, etc.  The vent screen aids in keeping the 

vent from becoming plugged, and the screen should 

be clean and properly installed.

Regulator Replacement

Older regulators are more likely to catastrophically 

fail because of worn or corroded parts.  Replace 

HSRL Series regulators over 20 years of age.  Other 

service or environmental conditions may dictate 

replacement of the regulator before it becomes 

20 years old.  Regulators that are installed on 

underground systems and in areas that are subject  

to sea salt (coastal) atmospheres should be inspected 

annually for external and internal corrosion  

and may require replacement sooner.  Refer to  

Fisher

®

 Bulletin LP-32 for additional information.

Water inside Regulators from Floods  

or Weather

Replace any regulator that has been flooded, has had 

water in the spring case or shows evidence of external 

or internal corrosion.  Checking for internal corrosion 

can be done by removing the closing cap and with the 

aid of a flashlight observing the condition of the relief 

valve spring, main spring, and internal spring barrel 

area.  A more detailed examination will require shutting 

down the gas system and complete removal of the 

adjusting screw.  Closely examine regulators installed 

with their vent horizontal for signs of corrosion.  

Correct any improper installations. 

Regulator Repair

Regulators that have been disassembled for repair 

must be tested for proper operation before being 

returned to service.  Only parts manufactured by 

Fisher should be used to repair Fisher regulators.  Be 

sure to give the complete type number of the regulator 

when corresponding with the factory.

The type number, orifice size, and spring range are 

on a label attached to the spring barrel.  The date of 

manufacture is stamped on the regulator.  Always 

provide this information in any correspondence with 

your Fisher Distributor regarding replacement parts 

or technical assistance.  If construction changes are 

made in the field, be sure that the regulator marking is 

also changed to reflect the most recent construction.

Содержание Fisher HSRL Series

Страница 1: ...standards and regulations of the LP Gas industry should install and service this equipment Things to tell the gas customer 1 Show the customer the vent or vent assembly or vent tube Stress that this opening must remain unobstructed at all times Tell the customer to check the vent opening after a freezing rain sleet storm or snow to make sure ice has not formed in the vent 2 Show the customer the s...

Страница 2: ...mate Weight 5 5 pounds 2 5 kg 1 The pressure temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded Orifice Size Wide Open Cg FOR RELIEF SIZING MAXIMUM OPERATING INLET PRESSURE TO OBTAIN GOOD REGULATING PERFORMANCE Inch mm psig bar 3 8 9 5 105 30 2 1 1 2 13 185 20 1 4 Table 1 Maximum Operating Inlet Pressure Table 2 Relief Performance Orifice siz...

Страница 3: ...scharge to the atmosphere through the vent An obstructed vent which limits air or gas flow can cause abnormally high pressure that could result in personal injury or property damage Failure to use a vent line on Indoor Installations can cause a hazardous accumulation of gas which could result in personal injury or property damage General Installation Instructions Before installing the regulator Ch...

Страница 4: ...ugh above ground level at least 18 inches 45 cm so that rain splatter cannot freeze in the vent Regulators Subjected to Heavy Snow Conditions Some installations such as in areas with heavy snowfall may require a hood or enclosure to protect the regulator from snow load and vent freeze over Horizontally Installed Regulators Horizontally mounted regulators such as found in single cylinder installati...

Страница 5: ... Series Figure 4 Basement Installation TO APPLIANCE VENT ASSEMBLY VENT OPENING MUST BE AT LEAST 3 FEET 0 91 meter HORIZONTALLY FROM ANY BUILDING OPENING BELOW IT VENT LINE BASEMENT FROM FIRST STAGE REGULATOR ...

Страница 6: ... wear or damage that may occur from external sources these regulators must be inspected and maintained periodically The frequency of inspection and replacement of the from the regulator s internal relief valve Vent lines should be at least 3 4 inch NPT pipe or 3 4 inch NPT size Gray PVC Schedule 40 Rigid Non metallic Electrical Conduit for above Ground Service per Underwriters Laboratories UL 651 ...

Страница 7: ...derground systems and in areas that are subject to sea salt coastal atmospheres should be inspected annually for external and internal corrosion and may require replacement sooner Refer to Fisher Bulletin LP 32 for additional information Water inside Regulators from Floods or Weather Replace any regulator that has been flooded has had water in the spring case or shows evidence of external or inter...

Страница 8: ... services described herein or their use or applicability We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Process Management Regulator Technologies Inc does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Process Management ...

Отзывы: