HSRL Series

6

Large volumes of gas may discharge 

through the regulator vent during 

internal relief valve operation, which 

can, if not controlled, result in fire or 

explosion from accumulated gas.

The HSRL Series regulators contain internal relief 

valves.  The internal relief valve in all units will give 

overpressure protection against excessive build-

up resulting from seat leakage due to worn parts or 

chips or foreign material on the orifice.  The amount 

of internal relief protection provided varies with the 

regulator type and the cause for the overpressure 

relief valve operation.  When the internal relief valve 

opens, gas escapes to the atmosphere through the 

regulator’s vent. 
Some type of additional external overpressure 

protection must be provided if the outlet pressure in 

an overpressure condition exceeds the inlet pressure 

rating of the gas system or downstream equipment.  

Common methods of external overpressure protection 

include relief valves, monitoring regulators, shutoff 

devices, and series regulation.

Maintenance

!

WaRninG

To avoid personal injury or equipment 

damage, do not attempt any maintenance 

or disassembly without first isolating 

the regulator from system pressure and 

relieving all internal pressure.
Regulators that have been disassembled 

for repair must be tested for proper 

operation before being returned to 

service.  Only parts manufactured by 

Fisher

®

 should be used for repairing 

Fisher regulators.  Relight pilot lights 

according to normal startup procedures.
Due to normal wear or damage that 

may occur from external sources, 

these regulators must be inspected and 

maintained periodically.  The frequency 

of inspection and replacement of the 

from the regulator’s internal relief valve.  Vent lines 

should be at least 3/4-inch NPT pipe or 3/4-inch 

NPT size, Gray PVC Schedule 40 Rigid Non-metallic 

Electrical Conduit for above Ground Service, per 

Underwriters Laboratories (UL

®

) 651.  To install the 

vent line, remove the vent screen and apply a good 

grade of pipe dope to the male threads of the line.  

Vent lines should be as straight as possible with a 

minimum number of bends.

adjustment

To increase the outlet pressure setting of the 

regulator, the adjusting screw  must be turned 

clockwise.  This requires removal of the closing 

cap.  To reduce the outlet pressure setting, turn 

the adjusting screw counterclockwise.  A pressure 

gauge should always be used to monitor downstream 

pressure while adjustments are being made.  Do not 

adjust the spring to produce an outlet pressure setting 

above the limit identified on the information label.  

After the spring adjustment has been completed, 

replace the closing cap.

Overpressure Protection

!

WaRninG

Some type of overpressure protection 

is needed if actual inlet pressure can 

exceed the outlet pressure rating.  

Overpressuring any portion of this 

equipment above the limits shown in 

the Specifications section may cause 

damage to regulator parts, leaks in 

the regulator, or personal injury due to 

bursting of pressure-containing parts or 

explosion of accumulated gas.
if any portion of the regulator is exposed 

to an overpressure condition that 

exceeds the limits in the Specifications 

section, it must be inspected for damage 

that may have occurred.

Содержание Fisher HSRL Series

Страница 1: ...standards and regulations of the LP Gas industry should install and service this equipment Things to tell the gas customer 1 Show the customer the vent or vent assembly or vent tube Stress that this opening must remain unobstructed at all times Tell the customer to check the vent opening after a freezing rain sleet storm or snow to make sure ice has not formed in the vent 2 Show the customer the s...

Страница 2: ...mate Weight 5 5 pounds 2 5 kg 1 The pressure temperature limits in this Instruction Manual or any applicable standard limitation should not be exceeded Orifice Size Wide Open Cg FOR RELIEF SIZING MAXIMUM OPERATING INLET PRESSURE TO OBTAIN GOOD REGULATING PERFORMANCE Inch mm psig bar 3 8 9 5 105 30 2 1 1 2 13 185 20 1 4 Table 1 Maximum Operating Inlet Pressure Table 2 Relief Performance Orifice siz...

Страница 3: ...scharge to the atmosphere through the vent An obstructed vent which limits air or gas flow can cause abnormally high pressure that could result in personal injury or property damage Failure to use a vent line on Indoor Installations can cause a hazardous accumulation of gas which could result in personal injury or property damage General Installation Instructions Before installing the regulator Ch...

Страница 4: ...ugh above ground level at least 18 inches 45 cm so that rain splatter cannot freeze in the vent Regulators Subjected to Heavy Snow Conditions Some installations such as in areas with heavy snowfall may require a hood or enclosure to protect the regulator from snow load and vent freeze over Horizontally Installed Regulators Horizontally mounted regulators such as found in single cylinder installati...

Страница 5: ... Series Figure 4 Basement Installation TO APPLIANCE VENT ASSEMBLY VENT OPENING MUST BE AT LEAST 3 FEET 0 91 meter HORIZONTALLY FROM ANY BUILDING OPENING BELOW IT VENT LINE BASEMENT FROM FIRST STAGE REGULATOR ...

Страница 6: ... wear or damage that may occur from external sources these regulators must be inspected and maintained periodically The frequency of inspection and replacement of the from the regulator s internal relief valve Vent lines should be at least 3 4 inch NPT pipe or 3 4 inch NPT size Gray PVC Schedule 40 Rigid Non metallic Electrical Conduit for above Ground Service per Underwriters Laboratories UL 651 ...

Страница 7: ...derground systems and in areas that are subject to sea salt coastal atmospheres should be inspected annually for external and internal corrosion and may require replacement sooner Refer to Fisher Bulletin LP 32 for additional information Water inside Regulators from Floods or Weather Replace any regulator that has been flooded has had water in the spring case or shows evidence of external or inter...

Страница 8: ... services described herein or their use or applicability We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Process Management Regulator Technologies Inc does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any Emerson Process Management ...