DVC2000 Digital Valve Controller
July 2009
3-2
The local user interface is available on all DVC2000
digital valve controllers. The interface consists of a
liquid crystal display, four pushbuttons, and a switch
for position transmitter configuration. The DVC2000 is
supplied with one of three different language packs
preinstalled, depending on the firmware revision and
ordering option. Language pack options are shown in
table 3-1. To configure the language, follow the
procedure outlined in the Basic Setup section. The
instrument must be powered with at least 8.5 volts and
3.5 mA to operate the local interface. Certain
procedures require up to 20 mA of current.
CAUTION
When accessing the terminals or
pushbuttons, proper means of
electrostatic discharge protection is
required. Failure to provide appropriate
protection can cause the valve to
move, resulting in valve/actuator
instability.
Status Information
The first (home) screen on the LCD that is displayed
after applying power to the instrument contains basic
status information. On an instrument that is calibrated
and operating properly, the flow chart in figure 3-1
shows the available information by pressing the right
(
) arrow key.
TRAVEL=##.#%—Current valve travel in percent of
calibrated travel.
##.# MA—Current input signal applied to the
instrument in mA.
##.## BAR—Current pressure output to the actuator in
the configured units (BAR, PSI or MPA).
SWITCH1—Current status of the optional limit switch
wired to ter41 and
−
42.
SWITCH2—Current status of the optional limit switch
wired to ter51 and
−
52.
FW#—Version of firmware running in the device.
HW#—Version of electronics hardware installed. The
first number (# : #) represents the main board, the
second number (# : #) represents the secondary
electronics.
TUNING = X—Current tuning set parameters
configured in the device.
PROTECTION—Indicates whether the local interface
is protected or not. With protection ON, the instrument
cannot be configured or calibrated with the local
pushbuttons.
Only with Optional
Transmitter / Limit Switches
TRAVEL = 66.8%
14.6 MA 0.92 BAR
SWITCH 1 = OPEN
SWITCH 2 = CLOSED
OFF
ON
PROTECTION
OFF
FW3:1, HW1:2
TUNING = C
Figure 3-1. Home Screen on the LCD
3
Содержание Fisher FIELDVUE DVC2000
Страница 40: ...DVC2000 Digital Valve Controller July 2009 3 14 3 ...
Страница 70: ...DVC2000 Digital Valve Controller July 2009 6 10 6 ...
Страница 71: ...Parts July 2009 7 1 7 7 Section 7 Parts Parts Ordering 7 2 Parts Kits 7 2 Parts List 7 2 7 ...
Страница 77: ...Principle of Operation July 2009 A 1 A A Appendix A Principle of Operation DVC2000 Operation A 2 A ...
Страница 80: ...DVC2000 Digital Valve Controller July 2009 A 4 A ...
Страница 104: ...DVC2000 Digital Valve Controller July 2009 Index 8 C Index ...
Страница 105: ......