Operating instruction 

EXD-HP1/2 Controller with ModBus 

communication capability 

 

 

 

Emerson Climate Technologies GmbH  

www.climate.emerson.com/en-gb

  

Date: 17.12.2020

 

Am Borsigturm 31 I 13507 Berlin I Germany 

 

EXD-HP12_OI_EN_DE_RU_1220_R06_865921.docx 

 

Code 

Parameter description and choices 

Min 

Max  Factory 

setting 

2P2 

Freeze alarm cut-out circuit 2 

-20 

2P5 

Freeze protection alarm delay, sec. 

199 

30 

2P- 

Superheat control circuit 2  

(Kp factor), fixed PID  Display 1/10K 

0.1 

10 

1.0 

2i- 

Superheat control circuit 2 (Ti factor),  

fixed PID 

350 

100 

2d- 

Superheat control circuit 2 (Td factor),  

fixed PID 

- Display 1/10K 

0.1 

30 

3.0 

2uH 

High superheat alarm mode circuit 2 

0 = diabled    

1 = enabled auto-reset 

 

 

 

2uA 

High superheat alarm setpoint (K) circuit 2 

16 

40 

30 

2ud 

High superheat alarm delay (Min) circuit 2 

15 

 

Selection for both circuits and discharge tempearature control 

Code 

Parameter description and choices 

Min 

Max  Factory 

setting 

Et 

Valve type 

0 = EXM / EXL 

1 = EXN 

 

 

 

Note: EXD-HP2 can drive two similar valves i.e. both valves must be 

either EXM/EXL or EXN. 

1E3 

Discharge Temperature Setpoint 

Start Setpoint 

70 

140 

85 

1E4 

Discharge Temperature Control band 

25 

20 

1E5 

Discharge Temperature limit 

100 

150 

120 

M O P  t a bl e  (° C )  

Refrigerant 

Min.

 

Max.

 

Factory 

setting

 

Refrigerant  Min. 

Max.  Factory 

setting 

R22 

-40 

+50 

+15  R452A 

-45 

+66 

+15 

R134a 

-40 

+66 

+15  R454A 

-57 

+66 

+10 

R410A 

-40 

+45 

+15  R454B 

-40 

+45 

+18 

R32 

-40 

+30 

+15  R454C 

-66 

+48 

+17 

R407C 

-40 

+48 

+15  R513A 

-57 

+66 

+13 

R290 

-40 

+50 

+15  R452B 

-45 

+66 

+25 

R448A 

-57 

+66 

+12  R1234ze 

-57 

+66 

+24 

R449A 

-57 

+66 

+12  R1234yf 

-52 

+66 

+15 

C o n t r o l   (v a l v e )   s t a r t - u p   be h a v i o r :   

(Parameter 1uu/2uu and 1u9/2u9) 

 

 

 

 

1uu/2uu: 

Min.:      10%  (<1 sec.) 

Default: 20% (< 1.5 sec.) 

Max.:     100% (< 6 sec.) 

 

 

 

U p l o a d / do w n l o a d   K e y :   F un c t i o n 

 

For serial production of systems/units, upload/download key allows the 

transmission of configured parameters among range of identical systems. 

U p l o a d i ng   p r o c e d u r e :    

(storing configured parameters in key) 

 

Insert the key while the first (reference) controller is ON and press 

 

button; 

the “

uPL

” message appears followed by “

End

” message for 5 seconds. 

 

Note: If the “

Err

” message is displayed for failed programming, repeat the above 

procedure. 

D o w n l o a d i ng   pr o c e d u r e : 

(configured parameters from key to other controllers) 

 

Turn off power to new controller 

 

Insert a loaded Key (with stored data from reference controller) into new controller 

and turn on the power supply. 

 

The stored parameters of the key will be downloaded automatically into the new 

controller memory; The “

doL

” message appears followed by a “

End

” message for 

5 seconds. 

 

The new controller with new loaded parameters setting will start to operate after 

End

” message disappears. 

 

Remove the key. 

 

Note: If the “

Err

” message is displayed for failed programming, repeat the above 

procedure. 

 

 

 

 
 
 
E r r o r / A l a r m   ha n d l i ng  

Alarm 

code 

Description 

Related 

parameter 

Alarm 

relay 

Valve 

What to do? 

Requires manual reset 

after resolving alarm 

1E0/2E0

 

Pressure sensor 1/2 error 

Triggered  Fully close  Check wiring connection and measure the signal 4 to 20 mA 

No 

1E1/2E0

 

Temperature sensor 1/2 error 

Triggered  Fully close  Check wiring connection and measure the resistance of sensor 

No 

1Ed

 

Discharge hot gas 

temperature sensor 3 error 

Triggered  Operating  Check wiring connection and measure the resistance of sensor 

No 

-

/2Π

-

 

EXM/EXL or EXN 

electrical connection error 

Triggered 

Check wiring connection and measure the resistance of winding 

No 

1Ad 

Discharge hot gas 

temperature above limit 

 

Triggered  Operating  Check valve opening/ check liquid flow for flash gas free/check 

discharge hot gas temperature sensor 

No 

1AF/2AF

 

Freeze protection 

1P4/2P4: 1  Triggered  Fully close  Check the system for cause of low pressure such as insufficient 

load on evaporator 

No 

1AF/2AF 

blinking

 

1P4/2P4: 2  Triggered  Fully close 

Yes 

1AL/2AL

 

Low superheat  

(<0,5K) 

1uL/2uL: 1  Triggered  Fully close 

Check wiring connection and operation of valve 

No 

1AL/2AL  

blinking

 

1uL/2uL: 2  Triggered  Fully close 

Yes 

1AH/2AH 

High superheat 

1uH/2uH: 1  Triggered  Operating  Check the system 

No 

1AP/2AP

 

Low pressure 

1P9/2P9: 1  Triggered  Operating  Check the system for cause of low pressure such as refrigerant 

loss 

No 

1AP/2AP 

blinking

 

1P9/2P9: 2  Triggered  Operating 

Yes 

Err 

Failed 

uploading/downloading 

Repeat again the procedure for uploading/downloading 

No 

Note: When multiple alarms occur, the highest priority alarm is displayed until being cleared, then the next highest alarm is displayed until all alarms are cleared. Only then will 

parameters be shown again. 

Содержание EXD-HP1

Страница 1: ... to comply with local regulations Inputs are not isolated potential free contacts needed to be used Disposal Electrical and electronic waste must NOT be disposed of with other commercial waste Instead it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment WEEE directive 2019 19 EU For further information contact...

Страница 2: ...selected parameter value Press or to increase or decrease the value Press to temporarily confirm the new value and display its code Repeat the procedure from the beginning press or to show To exit and save the new settings Press to confirm the new values and exit the parameters modification procedure To exit without modifying saving any parameters Do not press any button for at least 60 seconds TI...

Страница 3: ... 0 1 1 0 disable 1 enable 1u3 MOP set point C saturation temperature Factory setting according to selected refrigerant 1u0 The default value can be changed see MOP table Code Parameter description and choices Min Max Factory setting 1P9 Low pressure alarm mode circuit 1 0 2 0 0 disabled 1 enabled auto reset 2 enabled manual reset 1PA Low pressure alarm cut out circuit 1 0 8 17 7 0 1Pb Low pressure...

Страница 4: ...edure Do wnl oa di ng pr oc e dure configured parameters from key to other controllers Turn off power to new controller Insert a loaded Key with stored data from reference controller into new controller and turn on the power supply The stored parameters of the key will be downloaded automatically into the new controller memory The doL message appears followed by a End message for 5 seconds The new...

Страница 5: ...rbindungen vollständig sind Die Anlage darf erst dann in Betrieb genommen werden wenn alle Verbindungen hergestellt sind Für den gesamten elektrischen Anschluss sind die länderspezifischen Vorschriften einzuhalten Digitaleingänge sind spannungsbehaftet nur potentialfreie Schaltkontakte verwenden Entsorgung Elektro und Elektronik Altgeräte dürfen nicht mit anderem Gewerbemüll entsorgt werden Stattd...

Страница 6: ...ind passwortgeschützt Das werksseitig eingestellte Passwort ist 12 Taste länger als 5 Sek gedrückt halten eine blinkende 0 erscheint oder Taste drücken bis Passwort Standardwert 12 angezeigt wird drücken Passwort wird bestätig oder Taste drücken bis der gewünschte Parameter erscheint drücken der aktuell eingestellte Wert wird angezeigt oder Taste drücken der Wert wird vergrößert oder verkleinert d...

Страница 7: ... 2 PT5N 30 3 PT5N 10P FLR 1uu Ventilöffnungsgrad bei Start 10 100 20 1u9 Dauer der Ventilöffnung bei Start sec 1 30 5 Code Parameter Beschreibung und Auswahl Min Max Werk 1uL Alarm bei kleiner Überhitzung 0 2 1 0 aus für überfluteten Verdampfer 1 ein mit automatischer Rückstellung 2 ein mit manueller Rückstellung 1u5 Überhitzung Sollwert K wenn 1uL 1 2 Rückstell autom manuell wenn 1uL 0 Rückstellu...

Страница 8: ...erden Ko nfig ura tio nspar am e ter a uf de n Ko pie r sc hl üsse l lade n Der Referenz Regler muss eingeschaltet sein Kopierschlüssel einstecken und Taste betätigen Auf der Anzeige erscheint die Meldung uPL danach 5 Sekunden lang End Hinweis Falls die Fehlermeldung Err angezeigt wird Prozedur wiederholen Ko nfig ura tio nspar am e ter v om Ko pie r sc hl üssel a uf ande r e Re g le r übe r trag ...

Страница 9: ...ия Не подавайте питание на контроллер до окончания монтажа Проводите электрические подключения в соответствии с местными стандартами Входы не изолированы используйте сухие контакты Утилизация Электронные и электрические отходы НЕ ДОЛЖНЫ утилизироваться вместе с другими коммерческими отходами Обязанность пользователя передать их в предназначенное место для безопасной переработки электрического и эл...

Страница 10: ...етра Нажимайте или ля увеличения уменьшения значения параметра Нажмите для подтверждения нового значения Повторите процедуру от нажмите или для выбора Выход и сохранение новых значений Нажмите для подтверждения новых значений и покиньте процедуру изменения параметров Выход без сохранения Не нажимайте ничего в течение по крайней мере 60 секунд TIME OUT Возврат всех параметров к заводским настройкам...

Страница 11: ...испарителя 1 разрешён автовозврат 2 разрешён ручной возврат 1u5 Уставка перегрева K если 1uL 1 или 2 если 1uL 0 3 0 5 30 30 6 6 1u2 Функция MOP 0 1 1 0 запрещён 1 enable 1u3 Температура насыщения MOP Контур 1 C См таблицу MOP Заводская настройка соответствует выбранному хладагенту 1u0 и может быть изменена Код Описание параметра и возможности выбора Мин Макс Заводская настройка 1P9 Режим работы ав...

Страница 12: ...во включенный контроллер и нажмите кнопку появится сообщение uPL а затем через 5 сек сообщение End Внимание Появление сообщения Err означает сбой записи Повторите вышеописанную процедуру В ыгру зк а записьсконфигурированныхпараметровсключанадругиеконтроллеры Выключите питание нового котроллера Вставьте ключ с параметрами в новый контроллер и включите его питание Параметры с ключа автоматически выг...

Отзывы: