background image

 

1592009730 XW30-35VS GB r1.2 31.07.2015 

                            XW30VS  - XW35VS 

1/4 

XW30VS - XW35VS 

Digital controller for normal temperature with 

configurable relay  

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This  manual  is  part  of  the  product  and  should  be  kept  near  the  instrument  for  easy  and  quick 
reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot 
be used as a safety device. 

 

Check the application limits before proceeding. 

 

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 
ensuring the same and unchanged functionality. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not  expose to water or moisture: use the controller only within the operating limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent    formation  of 
condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” 
(see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model 

XW35VS,

 

100x64 

format,    is  a  microprocessor  based  controllers  suitable  for  applications  on 

medium or normal temperature refrigerating units.  

XW30VS

 is provided with 3 relay outputs to control compressor, alarm  and the lights. 

XW35VS

 is provided with 3 relay outputs to control compressor, evaporator fans  and the lights. 

It’s also provided with 2 NTC or PTC probe inputs, one for temperature control the second to display 
temperature of another point. 
An output allows the user to programme the parameter list with the 

“Hot Key”.

 

3.

 

CONTROLLING LOADS 

3.1

 

THE COMPRESSOR 

The  regulation  is  performed  according  to  the  temperature  measured  by  the  thermostat  probe  with  a 
positive  differential  from  the  set  point:  if  the  temperature  increases  and  reaches  set  point  plus 
differential the compressor is started and then turned off when the temperature reaches the set point 
value again. 
In  case  of  fault  in  the  thermostat  probe  the  start  and  stop  of  the  compressor  are  timed  through 
parameters “

COn

” and “

COF

”. 

3.2

 

FAST FREEZING 

When defrost is not in progress, it can be activated the keypad by holding the 

o

 key pressed for about 

3 seconds. The compressor operates in continuous mode for the time set through the “

CCt

” parameter. 

The cycle can be terminated before the end of the set time using the same activation key, 

o

 for about 

3 seconds. 

3.3

 

DEFROST 

The defrost interval is control by means of parameter “

EdF

”: (EdF=in) the defrost is made every “

IdF

” 

time,  (EdF=Sd)  the  interval  “IdF”  is  calculate  through  Smart  Defrost  algorithm  (only  when  the 
compressor is ON). 
Defrost  is  performed  through  a  simple  stop  of  the  compressor.  Parameter  “

IdF

”  controls  the  interval 

between defrost cycles, while its length is controlled by parameter “

MdF

”. 

 

3.4

 

CONTROL OF EVAPORATOR FANS – ONLY FOR XW35VS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC=C-n

   fans will switch ON and OFF with the compressor and

 not run

 during defrost

:

FnC= O-n

 fans will run continuously, but not during defrost  

 
After defrost, there is a timed fan delay allowing for drip time, set by means of the “Fnd” parameter. 

FnC=C-y

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC=O-y

   fans will run continuously also during defrost 

 
 
 
 
 
 
 
 
 
 

4.

 

KEYBOARD 

 

 

 

 

 

To  display  and  modify  target  set  point;  in  programming  mode  it  selects  a  parameter  or 
confirm an operation.  
By holding it pressed for 3s when max or min temperature is displayed it will be erased. 
 

 

To  see  the  max.  stored  temperature;  in  programming  mode  it  browses  the  parameter 
codes or increases the displayed value. By holding it pressed for 3s the fast freezing  cycle 
is started. 

 

To see the min stored temperature; in programming mode it browses the parameter codes 
or decreases the displayed value. 
 

 

 
By holding it pressed for 3s the defrost is started. 
 

 

 
Switch ON and OFF the light of the cold-room 

 

 
Switch ON and OFF the instrument. 

 

KEY COMBINATIONS 

 

 

 

 

To lock and unlock the keyboard.

 

 

 

 

To enter the programming mode. 

 

 

 

 

To exit the programming mode.

 

 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

Function 

 

ON 

The compressor is running 

 

FLASHING 

- Programming Phase (flashing with LED 

- Anti-short cycle delay enabled 

 

ON 

The fan is running 

 

FLASHING 

Programming Phase (flashing with LED 

 

ON 

The defrost is enabled 

 

FLASHING 

Drip time in progress 

 

ON 

The Fast Freezing cycle is enabled 

  

ON 

- ALARM signal 
- In “Pr2” indicates that the parameter is also present in “Pr1” 

 

ON 

The light is on 

 

4.2

 

HOW TO SEE THE MIN TEMPERATURE 

 

1.  

Press and release the 

n

 key. 

2.  

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

By pressing the 

n

 key or waiting for 5s the normal display will be restored. 

4.3

 

HOW TO SEE THE MAX TEMPERATURE 

 

1.  

Press and release the 

o

 key. 

2.  

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

By pressing the 

o

 key or waiting for 5s the normal display will be restored. 

4.4

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

To reset the stored temperature, when max or min temperature is displayed : 
1.

 

Press SET key until “rST” label starts blinking. 

 

N.B. After the installation RESET the temperature stored . 

 
 

Содержание dixell XW30VS

Страница 1: ...mpressor operates in continuous mode for the time set through the CCt parameter The cycle can be terminated before the end of the set time using the same activation key o for about 3 seconds 3 3 DEFROST The defrost interval is control by means of parameter EdF EdF in the defrost is made every IdF time EdF Sd the interval IdF is calculate through Smart Defrost algorithm only when the compressor is ...

Страница 2: ...d rES Resolution for C in 1 C de 0 1 C allows decimal point display dE 0 1 C in 1 C Lod Local display select which probe is displayed by the instrument P1 Thermostat probe P3 Display probe P2 not set it 1r2 not set it DEFROST EdF Defrost mode in interval mode The defrost starts when the time Idf is expired Sd Smartfrost mode The time IdF interval between defrosts is increased only when the compres...

Страница 3: ...m the outputs and the power connections Do not exceed the maximum current allowed on each relay in case of heavier loads use a suitable external relay N B Maximum current allowed for all the loads is 20A 8 1 PROBE CONNECTIONS The probe shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place the thermostat probe away from air streams to...

Страница 4: ...robe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe 0 255 min 30 Pr2 CH Type of regulation CL Ht CL Pr2 DISPLAY CF Temperature measurement unit C F C F Pr2 rES Resolution integer decimal point in de dE Pr1 Lod Local display P1 1r2 P1 Pr2 DEFROST EdF Defrost mode In Sd in Pr2 IdF Interval between defrost cycles 1 120h 8 Pr1 MdF Maximum length for 1 defrost 0 255 min 20 Pr1 dFd Displayin...

Отзывы: