2 • XR75CX I&O Manual
026-1210 Rev 4
3
Controlling Loads
3.1. Compressor
The regulation is performed according to the temperature
measured by the thermostat probe with a positive
differential (
HY
) from the setpoint: if the temperature
increases and reaches setpoint plus the differential, the
compressor is started and then turned OFF when the
temperature reaches the setpoint value again
.
In case of a fault in the thermostat probe, the start and stop
of the compressor are timed through parameters
Con
and
CoF
.
3.2. Defrost
Two defrost modes are available through the
tdF
parameter: defrost through electrical heater (
tdF
=
EL
) and
hot gas defrost (
tdF
=
in
).
•
EdF
=
in
, the defrost is made every
idF
time (the
standard method for the controller)
Other parameters are used to control defrost cycles: its
maximum duration (
MdF
) and two defrost modes: timed or
controlled by the evaporator’s probe (
P2P
).
At the end of defrost dripping time is started, its
duration is set in the
Fdt
parameter. With
Fdt
=
0
, the
dripping time is disabled.
3.3. Control of Evaporator
Fans
The fan control mode is selected by means of the
FnC
parameter:
•
FnC
=
C_n
: fans will switch ON and OFF with the
compressor and not run during defrost.
•
FnC
=
O_n
: fans will run even if the compressor is
OFF, and not run during defrost.
After defrost, there is a timed fan delay allowing for
drip time, set by means of the
Fnd
parameter.
•
FnC
=
C_y
: fans will switch ON and OFF with the
compressor and run during defrost.
•
FnC
=
O_y
: fans will run continuously during
defrost also.
An additional parameter called
FSt
provides the
setting of temperature, detected by the evaporator probe,
above which the fans are always OFF. This is used to make
sure that air is circulated only if this temperature is lower
than set in
FSt
.
3.3.1. Forced Activation of Fans
Managed by the
Fct
parameter, this function is
designed to avoid short cycles of fans that could occur
when the controller is switched ON or after a defrost, when
the room air warms the evaporator.
How it works: If the temperature difference between the
evaporator probe and the room probe is higher than the
Fct
parameter value, the fans will be switched ON. When
Fct
=
0
, the function will be
disabled.
3.3.2. Cyclical Activation of the Fans
With Compressor Off
When
FnC
=
C-n
or
C-y
(fans are working in parallel with
the compressor), by means of the
Fon
and
FoF
parameters,
the fans can carry out ON and OFF cycles even if the
compressor is switched OFF. When the compressor is
stopped, the fans will continue to work for the
Fon
time.
With
Fon
=
0
, the fans always remain OFF when the
compressor is OFF.
3.4. Light Relay
Configuration (PAR
oA2; Terminals 1-2)
The functioning of the auxiliary relay (terminals
1-2) can be set by the
oA2
parameter, according to the kind
of application needed. Possible settings are as follows:
Figure 3-1 - Compressor Temperature Regulation