xxxxxxxxxxxxxxxxxx XR44CH ISA GB r1.6 21.11.2016 

XR44CH 

4/5 

dAo 

Exclusion  of  temperature  alarm  at  start-up:  (0.0  to  24h00min,  res.  10min)  time 
interval between the detection of the temperature alarm condition after instrument power 
on and alarm signalling. 

OUTPUT RELAYS 

oA1 

First relay configuration AUX1: (dEF; FAn; ALr; LiG; AUS; onF; db; CP2; dEF2) dEF = 
defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; onF = 
always on when instrument on; CP2 = second compressor; dEF2 = second defrost. 

oA2 

Second  relay  configuration  AUX2:  (dEF;  FAn;  ALr;  LiG;  AUS;  onF;  db;  CP2; dEF2) 
dEF = defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; 
onF  =  always  on  when  instrument  on;  CP2  =  second  compressor;  dEF2  =  second 
defrost. 

oA3 

Third relay configuration AUX3: (dEF; FAn; ALr; LiG; AUS; onF; db; CP2; dEF2) dEF 
= defrost; FAn = do not select it; ALr = alarm; LiG = light; AUS = Auxiliary relay; onF = 
always on when instrument on; CP2 = second compressor; dEF2 = second defrost. 

DIGITAL INPUTS 

i1P 

Second digital input polarity: (oP; CL) oP = the digital input is activated by opening the 
contact; CL = the digital input is activated by closing the contact. 

i1F   

Second  digital  input  configuration:  (EAL;  bAL;  PAL;  dor;  dEF;  AUS;  Htr;  FAn;  ES) 
EAL = external alarm: “EA” message is displayed; bAL = serious alarm “CA” message is 
displayed; PAL = pressure switch alarm, “CA” message is displayed; dor = door switch 
function;  dEF  =  activation  of  a  defrost  cycle;  AUS  =  auxiliary  relay  activation  with 
oAx=AUSHtr = type of inverting action (cooling or heating); FAn = fan; ES = energy 
saving. 

did 

Digital input 1 alarm delay:  (0 to 255 min) delay between the detection of the external 
alarm condition and its signalling. 
When  i1F=  PAL,  it  is  the  interval  of  time  to  calculate  the  number  of  pressure  switch 
activation. 

nPS 

Number of pressure switch activation: (0 to 15) Number of activation, during the did 
or d2d interval, before signalling an alarm event (i1F, i2F=PAL).  
If the nPS activation during did or d2d time is reached, switch off and on the instrument 
to restart normal regulation. 

odC 

Compressor status when open door: (no; FAn; CPr;F_C;)  no = normal;  
FAn = normal; CPr = compressor OFF, F_C = compressor OFF. 

rrd 

Outputs restart after door open alarm: (n; Y) n = outputs follow the odC parameter.  
Y = outputs restart with a door open alarm.  

HES 

Delta temperature during an Energy Saving cycle:  (-30.0 to 30.0°C; -54 to 54°F) it 
sets the increasing value of the set point [SET+HES] during the Energy Saving cycle. 

OTHER 

HES 

Temperature increase during the Energy Saving cycle : (-30,0°C

30,0°C/-22÷86°F) 

it sets the increasing value of the set point during the Energy Saving cycle 

o-F 

Display during stand by: OFF = “OFF”; Lin: - - - 

Adr 

Serial  address:  (1  to  247)  identifies  the  instrument  address  when  connected  to  a 
ModBUS compatible monitoring system. 

PbC 

Type of probe: (PtC; ntC) it allows to set the kind of probe used by the instrument:  
PtC = PTC probe, ntC = NTC probe. 

onF 

On/Off key enabling: (nU; oFF; ES) nU = disabled; oFF = enabled; ES = not set it. 

dP1 

Thermostat probe display. 

dP2 

Evaporator probe display. 

dP3 

Third probe display- optional. 

dP4 

Fourth probe display- optional. 

rEL 

Software release for internal use. 

Ptb 

Parameter table code: readable only. 

9.

 

DIGITAL INPUTS  

The free voltage digital input is programmable by the i1F parameter. 

9.1

 

GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for did time delay before signalling the EAL 
alarm message. The outputs statuses don’t change. The alarm stops just after the digital input is de-
activated. 

9.2

 

SERIOUS ALARM MODE (I1F = BAL) 

When  the  digital  input  is  activated,  the  unit  will  wait  for  did  delay  before  signalling  the  CA  alarm 
message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

9.3

 

PRESSURE SWITCH (I1F = PAL) 

If  during  the  interval  time  set  by  did  parameter,  the  pressure  switch  has  reached  the  number  of 
activation of the nPS parameter; the CA pressure alarm message will be displayed. The compressor 
and the regulation are stopped. When the digital input is ON the compressor is always OFF. If the 
nPS activation in the did time is reached, switch off and on the instrument to restart normal 
regulation. 

9.4

 

DOOR SWITCH INPUT (I1F = DOR) 

It signals the door status and the corresponding relay output status through the odC parameter:  
no  =  normal  (any  change);  FAn  = Fan OFF; CPr = Compressor OFF; F_C = Compressor and fan 
OFF.  Since  the  door  is  opened,  after  the  delay  time  set  through parameter  doA, the door alarm is 
enabled, the display shows the message dA and the regulation restarts is rtr=YES. The alarm stops 
as  soon  as  the  external  digital  input  is  disabled  again.  With  the  door  open,  the  high  and  low 
temperature alarms are disabled. 

9.5

 

START DEFROST (I1F = DEF) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will 
restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety time 
is expired. 

9.6

 

SWITCH THE AUXILIARY RELAY (I1F = AUS) 

With oA3 = AUS the digital input switched the status of the auxiliary relay 

9.7

 

ENERGY SAVING (I1F = ES) 

The  Energy  Saving  function  allows  to  change  the  set  point  value  as  the  result  of  the  SET+  HES 
(parameter) sum. This function is enabled until the digital input is activated. 

9.8

 

ON OFF FUNCTION (I1F = ONF)  

To switch the controller on and off. 

9.9

 

DIGITAL INPUT POLARITY  

The digital input polarity depends on the i1P parameter. 
i1P = CL: the input is activated by closing the contact. 
i1P = oP
: the input is activated by opening the contact 

10.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows to connect the instrument to a 
monitoring system ModBUS-RTU compatible such as the XWEB500. The connection needs a special 
TTL/RS485 adapter: the XJ485CX

11.

 

INSTALLATION AND MOUNTING 

 

Instrument XR44CX shall be mounted on vertical panel, in a 29x71 
mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0 to 60°C. 
Avoid  places  subject  to  strong  vibrations,  corrosive  gases, 
excessive  dirt  or  humidity.  The  same  recommendations  apply  to 
probes. Let air circulate by the cooling holes. 
 

 

12.

 

ELECTRICAL CONNECTIONS 

The  instrument  is  provided  with  screw  terminal  block  to  connect  cables  with  a  cross  section  up  to 
2.5mm

2

.  Before  connecting  cables  make  sure  the  power  supply  complies  with  the  instrument’s 

requirements.  Separate  the  probe  cables  from  the  power  supply  cables,  from  the  outputs  and  the 
power  connections.  Do  not  exceed  the  maximum current allowed on each relay, in case of heavier 
loads use a suitable external relay. 

12.1

 

PROBE CONNECTION 

The  probes  shall  be  mounted  with  the  bulb  upwards  to  prevent  damages  due  to  casual  liquid 
infiltration.  It  is  recommended  to  place  the  thermostat  probe  away  from  air  streams  to  correctly 
measure  the  average  room temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

13.

 

USE THE HOT KEY  

13.1

 

HOW TO: PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When  the  controller  is  ON,  insert  the  “HOT-KEY”  and  push  UP  button;  the  “uPL  message 
appears followed a by a flashing “End” label. 

3.

 

Push SET button and the “End” will stop flashing. 

4.

 

Turn OFF the instrument, remove the “HOT-KEY” and then turn it ON again. 

 
NOTE: the “Err” message appears in case of a failed programming operation. In this case push again 
button if you want to restart the upload again or remove the “HOT-KEY” to abort the operation. 

13.2

 

HOW TO: PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert a pre-programmed HOT-KEY into the 5-PIN receptacle and then turn the Controller 
ON. 

3.

 

The  parameter  list  of  the  “HOT-KEY”  will  be  automatically  downloaded  into  the  Controller 
memory. The “doL” message will blink followed a by a flashing “End” label. 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the “HOT-KEY”. 
 

NOTE: the message “Err” is displayed for failed programming. In this case turn the unit off and then 
on if you want to restart the download again or remove the “HOT-KEY” to abort the operation. 

14.

 

ALARM SIGNALS 

Message 

Cause 

Outputs 

P1 

Room probe  failure 

Compressor output acc. to par. Con and CoF 

P2 

Evaporator probe  failure 

Defrost end is timed 

P3 

Third probe  failure 

Outputs unchanged 

P4 

Fourth probe  failure 

Outputs unchanged 

HA 

Maximum temperature alarm 

Outputs unchanged. 

LA 

Minimum temperature alarm 

Outputs unchanged. 

dA 

Door open 

Compressor and fans restarts  

EA 

External alarm 

Output unchanged. 

CA 

Serious external alarm (i2F=bAL)  All outputs OFF. 

CA 

Pressure switch alarm (i2F=PAL)  All outputs OFF 

oFF 

Controller in stand by 

All outputs OFF 

-  - - 

Controller in stand by 

All outputs OFF 

14.1

 

ALARM RECOVERY  

Probe alarms “P1”, “P2”, “P3” and “P4” start some seconds after the fault in the related probe; they 
automatically stop some seconds after the probe restarts normal operation. Check connections before 
replacing the probe. 

Содержание Dixell XR44CH

Страница 1: ...econd compressor is activated after a delay counter AC1 parameter Both compressor are switched off when the temperature set point is reached 3 2 2 Dual band activation With 2CC HAF the regulation is changed as follows a Activation of compressors The activation threshold of the first compressor is where T is temperature T SET Hy The activation threshold of the second compressor is where T is temper...

Страница 2: ... Press and release the UP key 2 The Hi message will be displayed followed by the maximum temperature recorded 3 By pressing the UP key again or by waiting 5 sec the normal display will be restored 5 3 HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 1 Keep the SET key pressed more than 3 sec while the max or min temperature is displayed rSt message will be displayed 2 To confirm the operation the...

Страница 3: ...nly for model with this option enabled P4 Fourth probe SET set point dtr percentage of visualization rEd X REP display optional P1 P2 P3 P4 SET dtr it selects which probe is displayed by X REP P1 Thermostat probe P2 Evaporator probe P3 Third probe only for model with this option enabled P4 Fourth probe SET set point dtr percentage of visualization dLy Display delay 0 20 0m risul 10s when the tempe...

Страница 4: ...d the display shows the message dA and the regulation restarts is rtr YES The alarm stops as soon as the external digital input is disabled again With the door open the high and low temperature alarms are disabled 9 5 START DEFROST I1F DEF It starts a defrost if there are the right conditions After the defrost is finished the normal regulation will restart only if the digital input is disabled oth...

Страница 5: ... Defrost type EL 0 in 1 ALt 2 in Pr2 dFP Probe for first defrost nP 0 P1 1 P2 2 P3 3 P4 4 P2 Pr2 dSP Probe for second defrost nP 0 P1 1 P2 2 P3 3 P4 4 nP Pr2 dtE First defrost termination temperature 55 0 C 50 0 C 67 F 122 F 8 0 Pr2 dtS Second defrost termination temperature 55 0 C 50 0 C 67 F 122 F 8 0 Pr2 idF Interval between defrost cycles 0 120 hours 6 Pr2 MdF Maximum length for first defrost ...

Отзывы: