26 • XR35CX I&O Manual
18.4.Wiring Types
Retail Solutions specifies Belden #8761 shielded
twisted pair cables for use as MODBUS wiring (or
Belden #82761 and Belden #88761 for plenum instal-
lations).
For MODBUS network wiring of XR35CX con-
trollers to E2, Belden #8641 (
Retail Solutions P/N
135-8641
) is the recommended wire type to use.
If the recommended cable is not available in your
area, be sure the wiring meets or exceeds the follow-
ing specs:
18.5.MODBUS Termination
Blocks
Because the XR35CX device has no on-board
means of termination, use the MODBUS termination
block (
P/N 535-2711
) for termination that can be
wired to the end of the cable segment using the three-
pin connector. Wire the two signal wires to the out-
side terminals, and connect the shield to pin
18
, keep-
ing the exposed shield wire length as short as possible
(3 inches ideal maximum length).
Shielded?
Yes
Conductor Type
Twisted Pair
Gauge
18 - 24 AWG
Capacitance between
signal wires
31 pF/ft or less
(9.45 m) or less
Capacitance between
signal and shield
59 pF/ft or less
(17.98 m) or less
Maximum Length
4000 ft/18 to 22 AWG
(1219.2 m)
2500 ft/24 AWG
(762 m)
Nominal Impedance
120
±50
Figure 18-9
- MODBUS Termination Block (P/N 535-2711)
SHIELD WIRE
(CONNECT TO
OF LAST DEVICE)
PIN 18
FROM OTHER
DEVICES
TO LAST DEVICE
AT END OF DAISY
CHAIN