8 • XR35CX I&O Manual
7
Parameters
Code
Parameter
Function
REGULATION
Hy
Differential
(0.1 to 25.5°C / 1 to 255°F)
Intervention differential for setpoint. Compressor Cut IN
is Se differential (
Hy
). Compressor Cut OUT is
when the temperature reaches the setpoint.
LS
Minimum setpoint
(-100°C to
SEt
/-148°F to
SEt
)
Sets the minimum value for the setpoint.
US
Maximum setpoint
(
SEt
to 110°C/
SEt
to 230°F)
Sets the maximum value for the setpoint.
ot
Thermostat probe calibration
(-12.0 to 12.0°C; -120 to 120°F)
Allows to adjust possible offset of the thermostat probe.
P2P
Evaporator probe presence
n
= not present: the defrost stops by time
y
= present: the defrost stops by temperature
oE
Evaporator probe calibration
(-12.0 to 12.0°C; -120 to 120°F)
Allows to adjust possible offset of the evaporator probe.
P3P
Third probe presence (
P3
)
n
= not present: the terminals 18-20 operate as digital in-
put
y
= present: the terminals 18-20 operate as third probe
o3
Third probe calibration (
P3
)
(-12.0 to 12.0°C; -120 to 120°F)
Allows to adjust possible offset of the third probe.
P4P
Fourth probe presence
(
n
= not present,
y
= present)
o4
Fourth probe calibration
(-12.0 to 12.0°C)
Allows to adjust possible offset of the fourth probe.
Ods
Outputs activation delay at start up
(0 to 255 min)
This function is enabled at the initial start up of the con-
troller and inhibits any output activation for the period of
time set in the parameter.
Ac
Anti-short cycle delay
(0 to 50 min)
Minimum interval between the compressor stop and the
following restart.
rtr
Percentage of the second and first probe for
regulation (0 to 100; 100 =
P1
, 0 =
P2
)
Allows to set the regulation according to the percentage
of the first and second probe, as for the following formula
(
rtr
(
P1
-
P2
)/
100
+
P2
).
CCt
Compressor ON time during continuous cycle
(0.0 to 24.0 hr, res. 10 min)
Allows to set the length of the continuous cycle: com-
pressor stays ON without interruption for the
CCt
time.
Can be used, for instance, when the room is filled with
new products.
CCS
Setpoint for continuous cycle
(-100 to 150°C)
Sets the setpoint used during the continuous cycle.
Con
Compressor ON time with faulty probe
(0 to 255 min)
Time during which the compressor is active in case of
faulty thermostat probe. With
Con
=
0
, compressor is al-
ways OFF.
Table 7-1
- List of Parameters