The ON/OFF Function
Parameters • 13
Hd1
First weekly holiday (Sun to
not used
)
Sets the first day of the week which follows the holiday
times.
NOTE:
Hd1
can be set also as
not used
value.
Hd2
Second weekly holiday (Sun to
not used
)
Sets the second day of the week which follows the holi-
day times.
NOTE:
Hd2
can be set also as
not used
value.
TO SET ENERGY SAVING TIMES (ONLY FOR MODELS WITH RTC)
iLE
Energy Saving cycle start during workdays
(0 to 23 hr 50 min)
During the Energy Saving cycle, the setpoint is increased
by the value in
HES
so that the operation setpoint is
SEt
+
HES
.
dLE
Energy Saving cycle length during workdays
(0 to 24 hr 00 min)
Sets the duration of the Energy Saving cycle on work-
days.
iSE
Energy Saving cycle start on holidays. (0 to 23
hr 50 min)
dSE
Energy Saving cycle length on holidays (0 to
24 hr 00 min)
TO SET DEFROST TIMES (ONLY FOR MODELS WITH RTC)
Ld1 to
Ld6
Workday defrost start (0 to 23 hr 50 min)
These parameters set the beginning of the 6 programma-
ble defrost cycles during workdays. (
e.g., When
Ld2
=
12.4 the second defrost starts at 12:40 during workdays
.)
Sd1 to
Sd6
Holiday defrost start (0 to 23 hr 50 min)
These parameters set the beginning of the 6 programma-
ble defrost cycles on holidays. (
e.g., When
Sd2
=
3.4 the
second defrost starts at 3:40 on holidays
.)
NOTE:
To disable a defrost cycle, set it to not used. (e.g., If
Ld6
=
not used
, the sixth defrost cycle is disabled.)
OTHER PARAMETERS
Adr
Serial address (1 to 244)
Identifies the controller address when connected to a
MODBUS compatible monitoring system.
pbC
Type of probe
Allows to set the kind of probe used by the controller:
Pt1
= Pt1000 probe
ntc
= NTC probe
CtC
= Standard CPC temp sensor
Set this pbC parameter to CtC to support standard CPC
temp sensors - factory default.
onF
ON/OFF key enabling
not used
= disabled
oFF
= enabled
ES
= not set it
dP1
Thermostat probe display
dP2
Evaporator probe display
dP3
Third probe display (optional)
dP4
Fourth probe display
rSE
Real setpoint
Shows the setpoint used during the energy saving cycle
or during the continuous cycle.
rEL
Software release
For internal use only.
Ptb
Parameter table code
Read only
Code
Parameter
Function
Table 7-1
- List of Parameters