1592001830 XC645D GB r3.4 04.09.2017.docx XC645D
44/50
Code Description
Cause
Action
Reset
A5
Liquid level
alarm
Input enabled
signaling only
Automatically
as soon as the input is disabled
A12
Configuratio
n alarms
See par. 18.1
A14
Load
maintenance
alarm
A load has
worked for the
hour set in the
SEr parameter
- signaling only
Manually:
reset the running hour of the compressor
(see par.
dtL
Discharge
Line
Temperature
Pb3 or Pb4
Temperature
Higher than
dtL
for the
dLd
time
delay
Digital Scroll
switched off
reduced
capacity
Automatically
as soon as the temperature becomes
lower than
dtL.
EA
External
alarm
The
configurable
dig. Input set
as EA is
activated
signaling only
Automatically
as soon as the input is disabled
InF
Inverter fan
alarm
The
configurable
dig. Input set
as EA is
activated
The analog out
set as INF is
switched off
Automatically
as soon as the input is disabled
FC01
…
FC04
Running
proof alarm
with
automatic
recover
The digital input
set as Co1.. Co6
has not been
activated by d1d,
… d4d time
The compressor
1..4 is switched
off and the safety
timers start
Automatic
–
when safety timers are over
LC01
…
LC04
Running
proof alarm
with manual
recover
5 running proof
alarms
happened in a
hour.
The compressor
1..4 is switched
off
Manual by means:
-
Controller off-on
-
Reset by keyboard
-
Reset by monitoring system
PrSH Low
superheat
Pre-allarm
The superheat is
less than: SH<
ASH2 + ASH0
for ASH1 time
Only warning
Automatic:
when superheat:
SH>ASH0+ASH2+1°C(2°F)
ALSH Low
superheat
allarm
The superheat is
less than: SH<
ASH2 for ASH3
time
Regulation
depends on
ASH4:
ASH4 = no
:
regulation not
affected.
ASH4 = yes
:
regulation is
stopped.
Automatic:
when superheat:
SH> ASH5 + ASH2
Содержание Dixell XC645D