17.10 Alarms
– fans section
LAF
:
Low pressure alarm
– fans section
: The measurement unit depends on the dEU
parameter: (FA04 ÷ HAF bar; -50.0÷HAF °C; FA04÷HAF PSI; -58÷HAF °F)
It’s
independent from the set point. When the value LAF is reached the LA2 alarm is enabled,
(possibly after the
AFd
delay time).
HAF
:
High pressure alarm
– fans section
: The measurement unit depends on the dEU
parameter: (LAF÷FA20 bar; LAF÷150.0 °C; LAF÷FA20 PSI; LAF÷302 °F).
It’s
independent from the set point. When the value HAF is reached the HA2 alarm is enabled,
(possibly after the
AFd
delay time).
AFd
:
Low and High pressure alarms delay
– fans section
: (0÷255 min) time interval
between the detection of a pressure alarm condition in the fans section and alarm
signaling.
HFC
Compressors off with high pressure (temperature) alarm for fans
no
= compressors are not influenced by this alarm
yES
= compressors are turned off in case of high pressure (temperature) alarm of fans
HFdP Digital Compressor Capacity percentage in case of high condenser pressure
(temperature) alarm
(0÷80%; with 0 the compressor is stopped)
dHF
Interval between 2 compressors turning off in case of high pressure (temperature)
alarm for fans
(0 ÷ 255 sec)
PnF: High pressure-switch intervention numbers
– fans section:
(0÷15 with 0 the manually
unlocking is disabled) if the high pressure-switch is enabled PnF times in the PiF interval,
the controller is locked.
It can be unlocked only manually
. See paragraph 0. Every time
the pressure-switch is enabled all the compressors are turned off and all the fans are
turned on.
PiF:
Pressure-switch interventions time
– fans section
(1÷15 min) Interval, linked to the
PEn parameter, for counting interventions of the high pressure-switch..
FPr
Number of fans engaged with faulty probe
. (0÷#fans).
17.11 Suction superheat
ASH0 Differential for low superheat pre-alarm.
(
0.1 to 30.0°C/ 1 to 60°F).
The low superheat pre-alarm warning is sent when the superheat (SH) is lower than ASH2
(low superheat alarm threshold) + ASH0, possibly after the ASH1 delay.
ASH1 Delay for signalling low superheat pre-alarm
(0÷255sec)
If the superheat is below the ASH2+ASH0 threshold for ASH1 time the low superheat
pre-alarm warning is sent.
ASH2 Low suction superheat alarm threshold (
0.1÷15.0°C/ 1÷30°F). With SH < ASH2 the
low superheat alarm is sent, possibly after the ASH3 delay
ASH3 Delay for signalling low superheat alarm
(0÷255sec)
If the superheat is below the ASH2 threshold for ASH3 time the low superheat alarm
message is sent.
ASH4 Switching off compressors with low superheat alarm
(No, Yes)
ASH4 = no: compressors keep on working even with low superheat alarm.
ASH4 = yES: compressors are stopped in case of low superheat alarm.
ASH5 Differential to restart regulation after of low superheat alarm with compressor stop
(0.1 to 15.0°C/ 1 to 30°F). In case of regulation stop (ASH4= yES), it restarts when SH >
ASH2+ASH5
ASH6 Delay to restart regulation after superheat > ASH2+ASH5 (
0÷255 min). If the
regulation is stopped because of low superheat alarm, it can restart when
SH>ASH2+ASH5 for the ASH6 time.
ASH7 Superheat value to enable hot gas injecting valve (
0.1 to 15.0°C/ 1 to 30°F)
With a relay set as hot gas injection valve, (oA2 or oA3 or oA4 = HGi), the relay is on with
SH < ASH7
– ASH8.
ASH8 Differential for ASH7
(
0.1 to 30.0°C/ 1 to 60°F)