12
1
4
Installation
Copeland ZX condensing units are delivered with a holding charge of neutral gas. The condensing unit should be located in such a place
to prevent any dirt, plastic bag, leaves or papers from covering the condenser and its fins. The unit must be installed without restricting
the airflow. A clogged condenser will increase the condensing temperature, thus reduce the cooling capacity, and lead to a high-pressure
switch tripping. Clean the condenser fins on a regular basis.
ZX
ZXD
ZXL
Model
Weight (kg)
Model
Weight (kg)
Model
Weight (kg)
ZX020BE
76
ZXD040BE
2
104
ZXL020BE
79
ZX025BE
79
ZXD050BE
3
112
ZXL025BE
81
ZX030BE
79
ZXD060BE
4
114
ZXL030BE
81
ZX040BE
1
91
ZXD075BE
5
122
ZXL035BE
93
ZX050BE
108
ZXL040BE
93
ZX060BE
112
ZXL050BE
106
ZX075BE
118
ZXL060BE
116
ZX076BE
121
ZXL075BE
121
Net Weight
Notes:
1
100 kg for models under 60 Hz TF5/7 and 50 Hz PFJ
2
109 kg for models under 60 Hz TF7
3
117 kg for models under 60 Hz TF7
4
121 kg for models under 60 Hz TF7
5
127 kg for models under 60 Hz TF7
Transport and Storage
Move ZX/ZXD/ZXL unit only with appropriate mechanical or handling equipment according to weight. Keep in the upright position. Do
not stack single boxes on top of each other without pallet in any case. Keep the packaging dry at all times.
Condensing Unit Handling