10
1
2
ZX CDU Connected to XWEB300D
ZX CDU connected to the Dixell XWEB300D with the Intelligent Store Solution Module using RS485 ModBUS.
Connect the ZX CDU to the ModBUS network as shown in Figure 5. Connect the network cable to the three-terminal connector on the
XWEB300D port that has been configured as ModBUS port (COM 12, 13, 14).
Connect port “13” of XWEB300D to port “D0485 +” of CoreSense
™
and port “12” of XWEB300D to port “D1485 -” of CoreSense
for RS485 communication.
Network Wiring
Dixell XWEB300D Serial Address - Wiring
•
Connect to the ModBUS network using cable with 2 or 3 shielded wires, minimum section 0.5mm
2
(e.g. BELDEN8772)
•
Do not connect shield to ground.
•
Do not connect the “Gnd” terminal.
•
Remember to draw a map of the line. This will help you to find an error if something is wrong.
•
RS485 devices are polarity sensitive.
Figure 6.
Correct Network Wiring
Figure 7 .
Incorrect Network Wiring
Figure 5.
XWEB300D Connected to the Intelligent Store Solution Module
Download the Program from Hot-Key to Controller
Step
Action
Phenomenon and Description
1
Turn-off the controller
2
Insert Hot-Key
3
Turn-on the controller
The “doL” message will blink followed a by a flashing “End” label (Note: if display “Err”,
it means it fails to download program to the controller. Please restart the process.)
4
Controller will restart working with the new parameters after 10 seconds
5
Remove Hot-Key