3. Electrical/Physical Data
4. Installation/Piping Instructions
A clearance of 8 inches from the wall (or the next
unit) is required from the unit’s left and rear panel; a
clearance of 20 inches is required from the unit's right,
top and front panels. (See diagams in section covering
Physical and Installation Requirements) Ensure that
the hot discharge air from one unit does not circulate
to another unit.
The unit is designed to mount on the ground, on a roof,
or on a wall. For ground mounting, the units should be
placed on a level solid concrete slab with rubber strips
between the feet and concrete, or other raised support
structure. For wall mounting, use a wall bracket system
designed for mounting condensing units or universal
metal framing strut and follow the manufacturer's
instructions. All mounting options must follow local
zoning and building codes.
Pipes should be sized for optimum performance and
good oil return, and for the full capacity range through
which this particular unit will need to operate. Follow the
ASHRAE guidelines for proper piping practice.
Model
Compressor
# of
Fans
Overall
Dimensions
(in)
Refrigerant
Connections
Receiver Capacity
(Lbs @ 90% Volume)
MCA Max
Fuse*
Defrost
Relay
Rating
†
(Amps)
Ship
Weight
(lbs)
L
W
H Liquid Suction R-134a
R-22
R-404A R-407A R-407C R-507A
R-448A* R-449A*
XFAL-020Z-CFV ZXI06KCE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
N/A
N/A
9.1
10
10
9.1
NA
NA
21.55
35
40
246
XFAL-020Z-TFC ZXI06KCE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
N/A
N/A
9.1
10
10
9.1
NA
NA
16.18
25
40
246
XFAL-030Z-TFC ZXI09KCE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
N/A
N/A
9.1
10
10
9.1
NA
NA
17.18
25
40
246
XFAL-035Z-CFV ZXI11KCE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
N/A
N/A
9.1
10
10
9.1
NA
NA
34.05
50
40
272
XFAL-040Z-CFV ZXI14KCE-PFV
2
16.7 40.5 48.9 1/2 S 7/8 S
N/A
N/A
13.4
14.8
14.7
13.4
NA
NA
40.1
60
40
274
XFAL-040Z-TFC ZXI14KCE-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
N/A
N/A
13.4
14.8
14.7
13.4
NA
NA
27.1
45
40
312
XFAL-050Z-TFC ZXI15KCE-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
N/A
N/A
13.4
14.8
14.7
13.4
NA
NA
28.85
45
40
323
XFAL-051Z-CFV ZXI16KCE-PFV
2
16.7 40.5 48.9 1/2 S 7/8 S
N/A
N/A
13.4
14.8
14.7
13.4
NA
NA
44.73
70
40
343
XFAL-060Z-TFC ZXI18KCE-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
N/A
N/A
13.4
14.8
14.7
13.4
NA
NA
33.98
50
40
341
XFAM-015Z-CFV ZS09KAE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
13.55
20
40
218
XFAM-015Z-TFC ZS09KAE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
11.05
15
40
219
XFAM-017Z-CFV ZS11KAE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
16.8
25
40
219
XFAM-017Z-TFC ZS11KAE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
14.05
20
40
219
XFAM-022Z-CFV ZS15KAE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
20.68
35
40
220
XFAM-022Z-TFC ZS15KAE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
14.3
20
40
219
XFAM-030Z-CFV ZS21KAE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
30.05
50
40
236
XFAM-030Z-TFC ZS21KAE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
20.05
30
40
236
XFAM-045Z-CFV ZS33KAE-PFV
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
37.35
60
40
285
XFAM-045Z-TFC ZS33KAE-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
29.98
50
40
280
XFAM-050Z-CFV ZS38K4E-PFV
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
41.85
70
40
292
XFAM-050Z-TFC ZS38K4E-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
28.85
45
40
292
XFAM-060Z-TFC ZS45K4E-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
31.98
50
40
299
XFAP-015Z-CFV ZS09KAE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
13.55
20
40
233
XFAP-015Z-TFC ZS09KAE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
11.05
15
40
234
XFAP-017Z-CFV ZS11KAE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
16.8
25
40
234
XFAP-017Z-TFC ZS11KAE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
14.05
20
40
234
XFAP-022Z-CFV ZS15KAE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
20.68
35
40
235
XFAP-022Z-TFC ZS15KAE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
14.3
20
40
234
XFAP-030Z-CFV ZS21KAE-PFV
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
30.05
50
40
251
XFAP-030Z-TFC ZS21KAE-TF5
1
16.7 40.5 33.1 1/2 S 7/8 S
10.7
10.5
9.1
10
10
9.1
9.7
9.7
20.05
30
40
251
XFAP-045Z-CFV ZS33KAE-PFV
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
37.35
60
40
300
XFAP-045Z-TFC ZS33KAE-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
29.98
50
40
295
XFAP-050Z-CFV ZS38K4E-PFV
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
41.85
70
40
307
XFAP-050Z-TFC ZS38K4E-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
28.85
45
40
307
XFAP-060Z-TFC ZS45K4E-TF5
2
16.7 40.5 48.9 1/2 S 7/8 S
15.7
15.5
13.4
14.8
14.7
13.4
14.2
14.3
31.98
50
40
314
Generator Requirements: In situations or locations where an electrical power generator is used for backup, the Copeland Scroll Outdoor Refrigeration Unit requires a supply voltage of