Label
Description
Default
Range
Compressor Safety
odS /
Output delay at start up (sec)
6
0 - 255
Con /
Compressor On time with faulty probe (min)
3
0 - 255
CoF /
Compressor OFF time with faulty probe (min)
3
0 - 255
2oF /
Compressor Minimum Off Time (sec)
120
1 - 900
HPn /
Number of high pressure switch activation
before compressor lock
5
0 - 15
bMP /
Bump start enable
YES
no, yes
dLn /
Number of activation of DLT in a hour to lock
compressor
4
0 - 15
Condenser Fan
MCS /
Minimum Condenser set point (°F)
70 - XFAP
80 - XFAL
-40 - 230
Low Side Control
dFd /
Display during defrost
dEF
DEF, Setpoint, Initial
Pressure, End Pressure
Fdt /
Drip time (min)
0
0 - 120
dPo /
Defrost at power-on
NO
no, yes
Sd1 /
Holiday defrost start 1 (hour)
6:00
nu, 0:00 - 23:50
Sd2 /
Holiday defrost start 2 (hour)
13:00
nu, 0:00 - 23:50
Sd3 /
Holiday defrost start 3 (hour)
21:00
nu, 0:00 - 23:50
Sd4 /
Holiday defrost start 4 (hour)
nu
nu, 0:00 - 23:50
Sd5 /
Holiday defrost start 5 (hour)
nu
nu, 0:00 - 23:50
Sd6 /
Holiday defrost start 6 (hour)
nu
nu, 0:00 - 23:50
Hd1 /
First Weekly holiday
nu
Sun - Sat
Hd2 /
second weekly holiday
nu
Sun - Sat
FnC /
Fans operating mode
on
cn, on, cy, oy
Compressor Protection
MC2 /
Adjustable current limit before trip (Amps)
MCA
0 - MCA
oCn /
Over Current Trips before lockout
5
0 - 15; 0 = always
automatic restart
PEn /
loss of phase trips number before lockout
5
0 - 15; 0 = always
automatic restart
Utn /
compressor trips before lockout
5
0 - 15; 0 = always
automatic restart
PiC /
Generate warning or shut the regulation when
phase imbalance
Trip
Warning, Trip
Serial Address
Adr /
Serial address
1
1 - 247