10. Refrigerant Liquid Temperature Valve Capacity Multiplier Correction Factors
Refrigerant Liquid Temperature Entering TXV
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
R-22
1.56 1.51 1.45 1.40 1.34 1.29 1.23 1.17 1.12 1.06 1.00 0.94 0.88 0.82 0.76
R-404A
2.00 1.90 1.80 1.70 1.60 1.50 1.40 1.30 1.20 1.10 1.00 0.90 0.80 0.70 0.50
R-507
2.00 1.90 1.80 1.70 1.60 1.50 1.40 1.30 1.20 1.10 1.00 0.90 0.80 0.70 0.50
R-134a
1.70 1.63 1.56 1.49 1.42 1.36 1.29 1.21 1.14 1.07 1.00 0.93 0.85 0.78 0.71
R-407A
1.75 1.68 1.61 1.53 1.46 1.39 1.31 1.24 1.16 1.08 1.00 0.92 0.84 0.76 0.68
R-407C
1.69 1.62 1.55 1.49 1.42 1.35 1.28 1.21 1.14 1.07 1.00 0.93 0.86 0.79 0.72
These factors include corrections for liquid refrigerant density and net refrigerating effect and are based on an
average evaporator temperature of 0°F. However, they may be used for any evaporator temperature from - 40°F
to + 40°F since the variation in the actual factors across this range is insignificant.
Evaporator Wiring
Typical Unit Cooler