ControlWave GFC IS Communication Interface Manual (CI-CW-GFC-ISTRAN)
Issued Nov-09
Specifications
5-1
Chapter 5 – Specifications
5.1 Environment
The IStran design supports operation inside a building or a weather-
proof enclosure only.
5.2 Operating Specifications
Table 5-1
provides the operating specifications for the IStran:
Table 5-1. IStran Operating Specifications
Description Specification
Operating
Temperature Range
-40
o
C to +70
o
C (-40
o
F to +158
o
F)
Operating Humidity
Range
15% to 95% RH (non-condensing)
Transient
Susceptibility
Field connected circuits designed to meet
requirements of
ANSI/IEEE C37.90.1-1989
(formerly
IEEE 472
) for surge withstand capability.
Vibration Effect
10 to 500 Hz at 1 g on any axis per
SAMA PMC-31-
1
without damage or impairment.
ESD Susceptibility
Field connected circuits designed to meet the
requirements of
IEC 801-2
for ESD withstand
capability up to 10KV.
EMI Compatibility
Designed to meet the susceptibility requirements of
IEC 801-3 level 2
(3V/M) from 500kHz to 500MHz.
Designed to meet
FCC Rules Part J, Subpart 15,
Class A
for radiated emissions.
Hazardous Locations
Designed to meet
NFPA
and
UL
requirements for
installation in Class I, Division 2, Groups C and D
hazardous locations.
Designed to meet
NFPA
and
UL
requirements for
connection to intrinsically safe devices located in
Division 1 locations.
The intrinsically safe device must be designed
and/or approved for the intended connection.
Содержание ControlWave GFC IStran
Страница 4: ...BLANK PAGE ...
Страница 6: ...ControlWave GFC IStran Instruction Manual vi Contents Issued Nov 09 ...
Страница 10: ...ControlWave GFC IS Communication Interface Manual CI CW GFC ISTRAN 1 4 Introduction Issued Nov 09 ...
Страница 26: ...ControlWave GFC IS Communication Interface Manual CI CW GFC ISTRAN 5 2 Specifications Issued Nov 09 ...
Страница 30: ...BLANK PAGE ...