background image

Product Data Document

420DS-12A

October 1, 2007 - Page 3

Integrated Pump Control 

SCADA RTU

Website:  www.EmersonProcess.com/Remote

Remote Automation Solutions

SCADA Packages 

The Bristol ControlWave Micro and ControlWave 

ExpressPAC integrated SCADA packages, from 

Emerson, are designed and built for out-of-the-box 

installation and startup. The assemblies are fully 

integrated units that combine the PLC/RTU with 

a variety of options commonly required in SCADA 

applications. These include a NEMA 4X rated en-

closure, power supply and battery backup options, 

termination options, display and operator input op-

tions, and wireless communication options. 

Historical Archive

Historical data is stored in three archive files in the 

ControlWave PLC/RTU flash memory. This ensures 

maximum data integrity even in the event of a 

SCADA communication network failure. The his-

torical data archives may be collected periodically 

on a scheduled or demand basis by the OpenBSI 

Harvester utility. This technique also minimizes 

communication bandwidth requirements significantly 

benefiting radio and cellular network architectures.

Daily Archive:

Stores 35 days of time-stamped minimums, maxi

-

mums, averages and totals

Hourly Archive:

Stores hourly time-stamped minimums, maximums, 

averages and totals

Trend Archive:
The Trend Archive stores instantaneous values at a 

fixed period from one minute to sixty minutes.

Setup and Configuration

As mentioned earlier, the

 

ControlWave pump control 

SCADA application is pre-programmed. The unit 

only needs site specific configuration through the 

easy-to-use set of web pages supplied with the ap-

plication software. These configuration web pages 

are accessible through the OpenBSI TechView 

utility. 

ControlWave MIcro  

PLC/RTU SCADA Package

 The ControlWave SCADA packages with the pre-

programmed pump controller application are ideal 

for integrating remote site measurement and control 

into the SCADA system.

Station Control Strategies:

Level control 
Pressure control 
Time control 
Pump lead/lag and pump alteration
Pump interlock and permissive conditions
Manual and PID VFD Control 

TechView allows easy connection to any 

ControlWave PLC/RTU through serial or Ethernet 

ports. The utility is essentially a web page browser 

that really simplifies menu navigation and PLC/RTU 

configuration. 

Содержание Control Wave SCADA RTU

Страница 1: ...o maintain level pressure and or flow Some sites may also have the need to control chemical feed measure rain level and detect intrusion events All of these are pre programmed and available for use to customize for the specific site When the application requires modifications or addi tions to the standard program Bristol ControlWave Designer allows unlimited customization by your engineering staff...

Страница 2: ... 2 tank level DI Intrusion or Motion Digital outputs Pump 1 2 start Pump 1 2 Stop Analog inputs Station flow Inlet pressure Outlet pressure Chlorine residual Clearwell level or tank level Analog outputs VFD speed control Chemical feed pump Counter inputs Station flow Rain gauge Triplex Booster or Lift Station Digital inputs Pump 1 2 3 status Pump 1 2 3 Remote Local 2 tank level DI Intrusion or Mot...

Страница 3: ...icantly benefiting radio and cellular network architectures Daily Archive Stores 35 days of time stamped minimums maxi mums averages and totals Hourly Archive Stores hourly time stamped minimums maximums averages and totals Trend Archive The Trend Archive stores instantaneous values at a fixed period from one minute to sixty minutes Setup and Configuration As mentioned earlier the ControlWave pump...

Страница 4: ... taneous values of pressure flow and level Setup and configuration may also be performed from the integral display keypad on the ControlWave PLC RTU SCADA package or via the SCADA system host HMI All configuration parameters are made available to OPC servers for compatibility with our OpenEnterprise SCADA software as well as third party SCADA software packages The configuration pages allow you to ...

Страница 5: ...nsducers Tank and wet well level measurement 5 to 700 feet 05 to 1 full scale accuracy Non fouling diaphragm options for lift station applications 4 20 mA or 0 5 V output AquaSensors Water Quality Instruments The AquaSensors DataStick provides a cost ef fective plug and play analytical measurement sys tem for continuous use in industrial environments DataStick communicates with ControlWave via a p...

Страница 6: ...prove the designs or specifications of such products at any time without notice All sales are governed by RAS terms and conditions which are available upon request RAS does not assume responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any RAS product remains solely with the purchaser and end user OpenEnterprise SCADA Host T...

Отзывы: