9.4
Add a unit's IP address to the Online Server in
RBM Network Administration
Prerequisites
Add an online server in RBM Network Administration.
The unit must have an IP address in the same network as that of the online server.
Procedure
1.
In RBM Network Administration, select
Online Server
>
Online Server Setup
.
The Online Server Setup window appears.
2.
Select a server name from the
Online Server
menu.
The
Online Server
box displays the AMS Machinery Manager database assigned to the
selected Online Server.
Active Units
lists the AMS Machinery Health Monitors
monitored by the selected Online Server.
3.
If data is being collected, click
Stop Data Collection
.
Data collection must be stopped to make changes.
The
Edit
buttons become active.
4.
Click
Edit
beside the
Active Units
box.
A
New Unit
field appears.
5.
Type in the IP address in
New Unit
and click
Add New
.
The unit appears in the
Active Units
list.
9.5
Online database configuration: overview
Configuring a database for an online monitoring application includes understanding how
each sensor is attached to the equipment and the corresponding connection to the AMS
6500 or AMS 2600.
In most cases, a AMS 2600 is not connected directly to sensors. Rather, it is connected
through coax cable with BNC connectors to a panel of monitoring modules. These
modules are connected to field wiring. Therefore, when building a database, it is
important to have a diagram that shows what sensors are connected to which monitoring
modules. In addition, an analyst who builds an online database needs to know if the
monitoring modules perform any signal conditioning on the input signals before passing
them through to their output connectors.
Data collection and analysis
MHM-97125-PBF-EN, R0
79
Содержание A6510
Страница 8: ...Introduction 4 MHM 97125 PBF EN R0 ...
Страница 16: ...Product Introduction 12 MHM 97125 PBF EN R0 ...
Страница 18: ...Sensor installation 14 MHM 97125 PBF EN R0 ...
Страница 28: ...Enclosure mounting 24 MHM 97125 PBF EN R0 ...
Страница 55: ...Default schema for network addressing Figure 6 11 Wire terminations MHM 97125 PBF EN R0 51 ...
Страница 56: ...Wire terminations 52 MHM 97125 PBF EN R0 ...
Страница 78: ...Software configuration 74 MHM 97125 PBF EN R0 ...
Страница 94: ...Data collection and analysis 90 MHM 97125 PBF EN R0 ...
Страница 104: ...System calibration 100 MHM 97125 PBF EN R0 ...
Страница 110: ...Data types 106 MHM 97125 PBF EN R0 ...
Страница 113: ...Index MHM 97125 PBF EN R0 109 ...