Cable recommendations
Table 5-1:
Cable pull location
Belden #
Application
Description
In steel conduit
9732
V707 / V727
9-pair, 24 AWG, individual foil shield, PVC jacket
9731
V727 / V745
12-pair, 24 AWG, individual foil shield, PVC jacket
In tray or aluminum
conduit
8168
V707
8-pair, 24 AWG, individual foil shield, PVC jacket, overall braid
shield
8175
V727 / V745
15-pair, 24 AWG, individual foil shield, PVC jacket, overall braid
shield
5.4
Physical network segment for the unit
Emerson recommends that customers run a dedicated physical network segment between
the database server and the unit, and follow these guidelines:
•
Handling & Care Guidelines, per EIA/TIA 568/569.
Note
EIA/TIA 568/569 requires only CAT5 cabling, but Emerson recommends that customers run at
least CAT5e to be compatible with future upgrades.
•
Pathways & Cable Trays, per EIA/TIA 569.
Note
Network cabling to the AMS 6500 should be in steel conduit.
5.5
Power circuit guidelines for the unit enclosure
The AMS 6500 is a laboratory grade instrument measuring millivolt level instrument
signals. The quality of the power provided to the unit is very important; follow specific
plant guidelines when running power to the unit enclosure.
Note
Adhere to IEEE 1100 specifications for powering and grounding electronic equipment.
Prediction side power specifications
Table 5-2:
DC
Nominal input voltage range
12 VDC – 24 VDC
Absolute input voltage range
10 VDC – 36 VDC
Maximum current draw
3.5 A
Nominal current draw
1.5 A
Cabling requirements
28
MHM-97125-PBF-EN, R0
Содержание A6510
Страница 8: ...Introduction 4 MHM 97125 PBF EN R0 ...
Страница 16: ...Product Introduction 12 MHM 97125 PBF EN R0 ...
Страница 18: ...Sensor installation 14 MHM 97125 PBF EN R0 ...
Страница 28: ...Enclosure mounting 24 MHM 97125 PBF EN R0 ...
Страница 55: ...Default schema for network addressing Figure 6 11 Wire terminations MHM 97125 PBF EN R0 51 ...
Страница 56: ...Wire terminations 52 MHM 97125 PBF EN R0 ...
Страница 78: ...Software configuration 74 MHM 97125 PBF EN R0 ...
Страница 94: ...Data collection and analysis 90 MHM 97125 PBF EN R0 ...
Страница 104: ...System calibration 100 MHM 97125 PBF EN R0 ...
Страница 110: ...Data types 106 MHM 97125 PBF EN R0 ...
Страница 113: ...Index MHM 97125 PBF EN R0 109 ...